Step # |
Option |
|
Default |
1 |
|
1st digit:
Bell Test at Restore:
0 = No test
8 = Test
|
2nd digit:
Power up Mode Report:
0 = No report
1 = Report sent
|
00 |
2 |
|
Enable Devices:
0 = Dialer
1 = Printer
|
2-6 Unused
7 = 24V system
|
0 – – – – – – 7 |
|
|
↑ (Do not change factory programming.) ↑ |
3 |
|
Options:
0 = Cadenced pulsing
1 = Code required at panel
2 = Trouble alert tone for
pre-alarm sound
3 = Pulsing fire bells
|
4 = Sound smoke delay
5 = Report fast restores
6 = Do not de-select.
7 = Time displays in
military format
|
– – – – – – 6 – |
4 |
|
1st digit:
(Display Rate)
0 = .5 sec
1 = 1 sec.
2 = 1.5 sec.
3 = 3 sec.
|
2nd digit:
0-7 = Max. number of
supervised touchpads
(0 means none.)
|
20 |
5 |
|
Misc. Options:
0 = Report walk tests
1 = Do NOT de-select
2 = Detect ground fault
|
3 = Sequential bell test
4 – 7 = Supervise bells 1-4
|
-1234567 |
6 |
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
|
Internal Zone Options (zones 1-8)
24-hour alarm (do not change default)
Select zones to be supervised for trouble
Unused (do not change default)
Zones will be Normally Open (do not change default)
Zone response speed 2 or 4
Zone response speed 3 or 4
Unused
Pre-alarm delay
Smoke verification delay
Number of zones that can be disabled
|
12345678
12345678
– – – – – – – –
12345678
12345678
– – – – – – – –
– – – – – – – –
– – – – – – – –
– – – – – – – –
12345678
|
7 |
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
7.10
|
External Zone Options (zones 9-16)
24-hour alarm (do not change default)
Select zones to be supervised for trouble
Unused (do not change default)
Zones will be Normally Open (do not change)
Zone response speed 2 or 4
Zone response speed 3 or 4
Unused
Pre-alarm delay
Smoke verification delay
Number of zones that can be disabled
|
90123456
90123456
– – – – – – – –
90123456
90123456
– – – – – – – –
– – – – – – – –
– – – – – – – –
– – – – – – – –
90123456
|
8 |
|
Total number of zones in system90847610 8 |
9 |
|
Dialer Options:
0 = Retry if fail
1 = Enable phone line 2
2 = Unused (do not select)
3 = Ground start (do not use
in UL installations)
|
4 = Enable TLM
5 = Answer ring detect
6 = Unused (do not select)
|
– 1 – – – 5 – 7 |
10 |
|
Total number of dialing attempts. |
0 |
11 |
|
Number of dialing attempts before dialer fail. |
0 |
12 |
|
Low AC hours (UL requires range of 6-12 hours.) |
6 |
13 |
|
Number of rings to activate downloading. |
10 |
14 |
|
Telephone # for reporting: |
|
14.1 |
Report alarms to:
1 = Ph. #1
2 = Ph. #2
3 = Ph. #3
4 = Ph. #4
|
Report troubles to:
5 = Ph. #1
6 = Ph. #2
7 = Ph. #3
8 = Ph. #4
|
1 – – – 5 – – – |
|
14.2 |
Report disabled zones to:
1 = Ph. #1
2 = Ph. #2
3 = Ph. #3
4 = Ph. #4
|
Report restores to:
5 = Ph. #1
6 = Ph. #2
7 = Ph. #3
8 = Ph. #4
|
1 – – – 5 – – – |
|
14.3 |
Report open resets to:
1 = Ph. #1
2 = Ph. #2
3 = Ph. #3
4 = Ph. #4
|
5-8 = Not used.
|
1 – – – – – – – – |
|
14.4 |
1-4 = Not used.
|
Report tests to:
5 = Ph. #1
6 = Ph. #2
7 = Ph. #3
8 = Ph. #4
|
– – – – 5 – – – |
|
14.5 |
Must Report:
1 = Ph. #1
2 = Ph. #2
3 = Ph. #3
4 = Ph. #4
|
Select Options:
5 = Line 1 is Touch-Tone
6 = Line 1 is Touch-Tone
7 = Use Touch-Tone only
8 = Enable 16-zone reporting
|
1 – – – – – – – |
15 |
|
Computer phone number for up/downloading. |
[blank] |
16 |
16.1
16.2
16.3
16.4
|
Central station phone numbers:
Phone number 1
Phone number 2
Phone number 3
Phone number 4
|
5551234567890
– – – – – – – –
– – – – – – – –
– – – – – – – –
|
17 |
17.1
17.2
17.3
17.4
|
Central station account numbers:
Account number 1
Account number 2
Account number 3
Account number 4
|
005207
– – – – – – – –
– – – – – – – –
– – – – – – – –
|
18 |
18.1
to
18.4
|
1st digit:
# of attempts before
switching to next account
for Accounts 1-4.
|
2nd digit:
Dialer frmt Accts. 1-4:
0 = SIA8 |
4 = BFSK23 |
1 = FSK1 |
5 = SIA20 |
2 = Not used |
6 = SK4+2 |
3 = BFSK14 |
|
1 0 |
19 |
19.1
to
19.4
|
Phone opts for accts 1-4:
0 = Unused
1 = Use line 1 only
2 = Use line 2 only
|
3 = 9000 Direct (do not select)
4-9 = Unused (do not select)
|
– – – – – – – – |
20 |
20.1
20.2
20.3
20.4
20.5
20.6
|
Duration of delays:
Bell shutdown time delay
Unused (Do not change)
Pre-alarm delay
Smoke verification delay
Smoke reset time
Unused (Do not change)
|
90
30
30
30
2
24
|
21 |
|
Test Time |
|
000000 |
22 |
22.0
22.1
22.2
to
22.9
|
Secret Codes:
Installer’s code
Main user’s code
Other users (basicfunctions – can reset
alarms and disable zones).
|
123456
1111
[blank]
|
23 |
23.1
23.2
23.3
23.4
23.5
23.6
|
Relays (1-4) and bells (5-8) to activate for:
Pre-alarm conditions
Tamper alarms
Special (auxiliary) alarms
Fire alarms
Trouble conditions 1
No silence conditions
|
– – – – – – – –
– – – – – – – –
– – – – – – – –
– – – – 5678
– – – – – – –
– – – – – – – –
|
24 |
24.0
24.1
to
24.16
|
Alarm relay (1-4), bells (5-8) activate by zN.
Bells and relays Activate during a fire drill.
Bells and relays to activate for alarms in
zones 1-16.
|
– – – – – – – –
– – – – – – – –
|
25 |
25.1
to
25.16
|
1st digit: Audible signal
0 = Bells can shut down
2 = Cross alarm delay
4 = No manual bell sound
8 = No auto bell shutdown
A = Cross alarm and
no shutdown
|
2nd digit: Zone type
0 = Fire drill
1 = Fire
3 = Panic
5 = Tamper
6 = Sprinkler
7 = Undefined auxiliary
8 = Water
9 = Heat
A = Cold
B = Local
C = Unused
|
8 1 |
26 |
26.1
to
26.16
|
Zone location descriptions. (Click HERE for word list)
Press 1 to toggle words from first list and press
2 to toggle words from second list, ENTER to save.
|
WORDS
|
27 |
|
Length of temporal (pulsing) pattern |
32 |
28 |
28.1
28.2
28.3
28.4
|
Cadence pattern (used with step 27)
First group of 8 bits
Second group of 8 bits
Third group of 8 bits )
Fourth group of 8 bits
(Each substep controls up to four seconds.
|
12345678
12345678
12345678
– – – – – – – –
|