Silent Knight 5204 Trouble

0 Fire drill (with ALARM, ALARM MEMORY, or TROUBLE LED).
1 through 4 Zone numbers (with ALARM, ALARM MEMORY, or TROUBLE LED).
A “c” in front of the number indicates a supervisory sprinkler zone.
E7 Indicates trouble with the EEPROM memory.
F0 5230 annunciator power trouble.
F1 through F3 Indicates trouble with a particular annunciator.
A1 through A2 Indicates trouble with a particular bell output.
P3 Indicates a short between Earth Ground and Common Ground. To determine the
location of the short, remove field wiring circuits until the control returns to normal
operation.
P4 Indicates a short between Earth Ground and loop or bell power. To determine the
location of the short, remove field wiring circuits until the control returns to normal
operation.
P0 Indicates that the printer is out of paper.
dc Low battery condition.
Ac Low AC condition.
dF Dialer failed to communicate or Data lost during an attempt to transmit data to the
central station.
L1 Phone Line 1 Fault
L2 Phone Line 2 Fault
-0 Fire drill
-2 Walk test
-4 Downloading
-5 Zone test
-6 HEX PROGRAMMING mode
-7 STEP PROGRAMMING mode
-8 SET DATE mode
-9 SET TIME mode
2-, 3-, 4-, 5-
6-, 7-, 8-, 9-

User must enter a code to perform the desired function with these prompts.