First Alert 110C Program

Enter Program Master Code + 8 + 0 + 0 (Display should show 20)
or Power down then back up and press * and # within 1 minute
(If exiting programming you can re-enter within 1 minute by pressing * and #)
Move to Location * + Location
View Location # + Location (Display will read off one digit at a time)
Exit Program 1. *98 OR 2. *99 if needing to re-enter programming later by Code + 8 + 00

*20 Master Code I_4_I_1_I_1_I_0_I
*21 Quick Arm Enable I_1_I 0 = No
1 = Yes
*22 Keyswitch Enable I_0_I 0 = No
1 = Yes
*23 Force Bypass Enable I_0_I 0 = No
1 = Yes
*27 Audible Exit Warning
(not on older FA-110C’s)
I_1_I 0 = No
1 = Yes
*28 Confirmation of Arming Ding I_0_I 0 = No
1 = Yes
*29 Fire Sounder No Timeout I_1_I 0 = No
1 = Yes
*30 Alarm Bell Timeout I_2_I 1 = 4 minutes
2 = 8 minutes
3 = 12 minutes
4 = 16 minutes
*31 Zone 1 Definition I_?_I 0 = Zone Disabled
1 = Entry/Exit
2 = Not Used
3 = Instant/Perimeter
4 = Interior/PIR
5 = Trouble by Day
6 = 24 hr Silent (Holdup)
7 = 24 hr Audible (Police Panic)
8 = 24 hr Auxiliary (Medical)
9 = Fire without Timeout (Smokes)
#10 = Interior with Delay
*32 Zone 2 Definition I_?_I
*33 Zone 3 Definition I_?_I
*34 Zone 4 Definition I_?_I
*35 Zone 5 Definition
(Hardwire Smokes this zone)
I_?_I
*36 Zone 6 Definition I_?_I
*37 Zone 7 Definition
(Panic * & #)
I_7_I
*38 Entry Delay I_2_I Exit Delay = Entry + 15 seconds
1 = 20 seconds
2 = 30 seconds
3 = 45 seconds
4 = 60 seconds
5 = 90 seconds
*39 Zone 3 Response to open I_0_I 0 = 400ms
1 = 10ms
*40 PABX Access Code I_ _I_ _I_ _I_ _I (If 9 is needed to dial add here)
*41 Primary Phone
(12 digits)
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
End Phone with * # + 11 = * # + 12 = # # + 13 = 2.5 second pause
*42 Secondary Phone I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
Pager only available on VERY new 4110-DL’s,
pager will not work if Account starts with 0
*43 Subscriber Account I_ _I_ _I_ _I_ _I
Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15
*44 Report Format I_7_I 0 = 3/1, 4/1 Ademco L/S Standard
1 = 3/1, 4/1 Radionics Standard
2 = 4/2 Ademco L/S Standard
3 = 4/2 Radionics Standard
6 = 4/2 Ademco Express
7 = Contact ID
8 = 3/1, 4/1 Ademco L/S Expanded
9 = 3/1, 4/1 Radionics Expanded
*45 Phone System Select I_3_I 0 = Pulse Dial
1 = DTMF Dial
2 = Pulse Dial, CS on Watts Line
3 = DTMF Dial, CS on Watts Line
*46 Sescoa/Radionics Select I_0_I 0 = Radionics
1 = Sescoa
*47 15 Sec Burg Dial Delay I_0_I 0 = No
1 = Yes
*48 Periodic Test Message I_0_I 0 = None
1 = 24 Hours
2=Weekly
*49 Split/Dual Reporting I_0_I
To Primary Phone To Secondary Phone
0 = All Reports Backup Only
1 = Alarms, Restore, Cancel All Other Reports
2 = All Reports except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All Reports
4 = All Reports except Open/Close, Test All Reports
5 = All Reports (Dual Reporting) All Reports
*50
Keypad Medical/Fire             1 & *           I_1_I                                   (Silent, sends 95)
3 & # I_1_I (Audible, sends 96)

(This section may not be available on older models, display will show EE)

*51 Zone 1 Report Code I_1_I_0_I
*52 Zone 2 Report Code I_1_I_0_I
*53 Zone 3 Report Code I_1_I_0_I
*54 Zone 4 Report Code I_1_I_0_I
*55 Zone 5 Report Code I_1_I_0_I
*56 Zone 6 Report Code I_1_I_0_I
*57 Zone 7 Police Panic Report Code I_1_I_0_I
*58 Zone 8 Duress Report Code I_1_I_0_I
*59 Zone 9 Tamper Report Code I_0_I_0_I
*60 Trouble Report Code I_1_I_0_I (Fire Trouble)
*61 Bypass Report Code I_0_I_0_I
*62 AC Loss Report Code I_1_I_0_I
*63 Low Bat Report Code I_1_I_0_I
*64 Test Report Code I_0_I_0_I
*65 Open Report Code I_0_I
*66 Close Report Code I_0_I
*68 Cancel Report Code I_1_I_0_I
*69 Group Restores Trouble/Bypass I_0_I
*70 Alarm Restore Code I_0_I
*71 Trouble Restore Code I_0_I_0_I
*72 Bypass Restore Code I_0_I_0_I
*73 AC Restore Code I_0_I_0_I
*74 Low Bat Rest Code I_0_I_0_I
*93 Reports Per Armed Period I_0_I 0 = 10 Reports
1 = Unlimited
*94 Download Phone Number I_1_I_8_I_0_I_0_I_6_I_8_I_2_I_1_I_6_I_9_I_0_I_ _I
*95 Ring Count I_# 15_I 0 to #15 (#15 = Answer Machine)
*96 Reinitialize Download (No Value needed, keypad will just beep)
*97 Default Panel (No Value needed, keypad will beep and default panel)
*98 Exits Program Mode (Will not allow re-entry with Installer Code + 8 + 0 + 0)
*99 Exits Program Mode (Will allow re-entry with Code + 8 + 0 + 0)