Home Firelite Firelite MS-5024 Firelite MS-5024 Firelite MS5024 / US52014 UDE Basics This is a Fire system, powering down is usually illegal! Zones 5 Fire Zones Silence Alarm Press SILENCE Reset System Press RESET (Display will show rES for 6 seconds) (Displays active alarm or 1st previous event) (Displays newest Alarms in memory) (Displays previous Alarms in memory) Zone Disable (If zone is in trouble only) 1. Press MODE 2. Press 3472 + ENTER/STORE 3. Enter Zone to disable(1 to 5) 4. Press ENTER/STORE (Display goes blank) (Display shows “d”) (Zone will appear at far right of display) (Trouble LED will blink, d__ 1 to 4 displays) Zone Re-Enable (If zone was disabled with a trouble) 1. Press MODE 2. Press 3622 + ENTER/STORE 3. Enter Zone to re-enable (1 to 5) 4. Press ENTER/STORE (Display goes blank) (Display shows flashing “E”) (Zone will appear at far right of display) (Trouble LED will turn OFF) Fire Drill 1. Press MODE 2. Press 3745 + ENTER/STORE 3. Press RESET to exit (Display goes blank) (Display shows “dril”) Lamp Test MODE + 5267 + ENTER/STORE (turns on all System LED’s for 5 seconds) Walk Test 1. Press MODE 2. Press 9255 + ENTER/STORE 3. Press 6676 + ENTER/STORE to exit (Display goes blank) (Trouble light begins blinking) History Mode 1. Press MODE 2. Press 4478 + ENTER/STORE 3. SILENCE twice to erase History 4. Press 6676 + ENTER/STORE to exit (Display goes blank) Displays newest Alarms in History Displays previous Alarms in History Displays d__1 = Zone 1 Disabled F__4 = Trouble Zone 4 d__2 = Zone 2 Disabled F__5 = Trouble Zone 5 d__3 = Zone 3 Disabled F__A = Annunciator Fault d__4 = Zone 4 Disabled F__E = Earth Fault d__5 = Zone 5 Disabled Lo_b = Low Battery E__1 = Zone 1 Enabled no_b = No Battery E__2 = Zone 2 Enabled PH_1 = Primary C. S. Number Comm Fault E__3 = Zone 3 Enabled PH_2 = Secondary C. S. Number Com Fault E__4 = Zone 4 Enabled bEL1 = Bell 1 Fault or Disabled E__5 = Zone 5 Enabled bEL2 = Bell 2 Fault or Disabled A__1 = Alarm Zone 1 no_1 = Primary Phone Line Fault A__2 = Alarm Zone 2 no_2 = Secondary Phone Line Fault A__3 = Alarm Zone 3 SUP1 = Supervisory Alarm Zone 1 A__4 = Alarm Zone 4 SUP2 = Supervisory Alarm Zone 2 A__5 = Alarm Zone 5 SUP3 = Supervisory Alarm Zone 3 F__1 = Trouble Zone 1 SUP4 = Supervisory Alarm Zone 4 F__2 = Trouble Zone 2 SUP5 = Supervisory Alarm Zone 5 F__3 = Trouble Zone 3 _AC_ = AC Power Loss rES_ = System Reset