FBI Legend 100 Program

If Master Code is lost the panel MUST be downloaded or defaulted
Enter
Programming

CODE * 123456 1

Programming starts at Location 000 and ask what level of programming you want
Press 0 (Toggle) to toggle through below programming options

Quick < This only gets you into locations up to 015
Intermediate < similar to Quick
Partitioned < Zones, Users, Keypad Partitioning
Advanced < This gets you into every location

After choosing press STAY

Options Code + * + Installer Code + 1 = Enter Programming
Code + * + Installer Code + 2 = Time/Date Setup
Code + * + Installer Code + 3 = Walk Test without Bell
Code + * + Installer Code + 4 = Walk Test With Bell
Code + * + Installer Code + 5 = Default Panel
Code + * + Installer Code + 6 = System Log View (Event Buffer)
Moving to
Location
* + STAY + 3-digit location
Program Keys
STAY saves data and moves to next programming location
BYPASS goes back to previous programming location
0 toggles options within location
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
Exit
Programming
Press * and # at same time (or SHIFT and ABORT)

Communications
Question Suggest Variables
000 Select Program Level Advanced Quick
Intermediate
Partitioned
Advanced
001 Callback Number Leave Blank Up to 32 digits
002 Dump Telephone Number Leave Blank Up to 32 digits
003 CS 1 Receiver Phone # 18xxxxxxx Up to 32 digits
SHIFT + 2 (B) = *
SHIFT + 3 (C) = 3 second delay
SHIFT + 4 (D) = #
To erase move cursor to beginning
of number by pressing CODE then * 8
004 CS 1 Receiver Type 20PPS 2300 10PPS 1400
10PPS 2300
20PPS 1400
20PPS 2300
40PPS 1400
40PPS 2300
BFSK (Radionics)
FBII (4x3x1)
005 CS 1 Parity Selection No
Yes = Report Parity Enabled
No = Report Parity Disabled
006 Format CS#1 4×2 Standard
Extended
Partial Extended
4×2
007 CS 2 Receiver Phone # 18xxxxxxx Up to 32 digits
008 CS 2 Receiver Type 20PPS 2300 10PPS 1400
10PPS 2300
20PPS 1400
20PPS 2300
40PPS 1400
40PPS 2300
BFSK (Radionics)
FBII (4x3x1)
009 CS 2 Parity Selection No
Yes = Report Parity Enabled
No = Report Parity Disabled
010 Format CS#2 4×2 Standard
Extended
Partial Extended
4×2
011 # of Partitions 1 1 to 8
012 CS#1 Account Number Up to 4-digits SHIFT 1 = A
SHIFT 2 = B
SHIFT 3 = C
SHIFT 4 = D
SHIFT 5 = E
SHIFT 6 = F
013 CS#2 Account Number Up to 4-digits
014 Installer Code 123456 Leave alone
015 Tone Dialing Yes
Yes = Touch Tone Dialing
No = Pulse Dialing
016 CS Dialer Enable Yes
Yes = Communicator Enabled
No = Communicator Disabled
017 Remote Commands Enable
(Downloader Arm/Disarm etc)
Yes
Yes = Allow Remote Commands
No = No Remote Commands
018 Remote Arm Enable Yes
Yes = Remote Arming Enabled
No = Remote Arming Disabled
019 Remote Bypass Enable Yes
Yes = Remote Bypassing Enabled

No = Remote Bypassing Disabled
020 # Attempts (Dialing Attempts) 08 01 to 16 Attempts (08 = Default)
021 # of Rings to Pickup 08 01 to 16 Rings (08 = Default)
022 Extended Antijam No
Yes = 4 Second wait until Dialing
No = 30 Second wait until Dialing
023 Extended Ack No
Yes = 120 Sec wait for Ack from CS

No = 30 sec wait for Ack from CS
User Attributes (Pick a user in 025 and program individual attributes)
Question
024 Select User Number 01 to 16, 000 = Skip
025 User Authority Level
(User Code 1 is always Level 1)
Level 1
Level 2
Level 3
Level 4
Arm/Disarm/Bypass/Program Users
Arm/Disarm/Bypass
(Arm/Disarm)
(Arm only, Temp User)
026 User O/C CS ID 1 to F (What digit sends for Opening/Closings)
027 User Partition Assignment
(Which Partition for this Code)
YNNNNNNN (Use INSTANT and CODE to move left/right)
(0 toggles Y/N for each of the 8 partitions)
028 User Master Partition Not Sure 1 to 8
System Attributes
Question Suggest Variable
029 Open/Close CS #1 Report Path CS#1 Only CS#1 Only
CS#2 Only
CS#1 & CS#2
CS#1 BU CS#2 (CS2 as Backup)
CS#2 BU CS#1 (CS1 as Backup)
None (Reports)
030 Test to CS#1 (Test Signals) None
031 Test Frequency Sunday
12 Hour Wednesday
24 Hour    Thursday
Sunday Friday
Monday Saturday
Tuesday
032 Enable 16 Zone No
Yes = Expansion Board Present
No = System uses 8 Zones
033 Byp Tran Type On Bypass
On Bypass = Sends signal on Bypass
On Arming = Sends signal on Arming
034 Auto Unby En Yes
Yes = Bypassed Zns unbypass w/Disarm
No = Bypassed Zns Manually Unbypassed
035 Arm Out Lev High
High = Trigger Voltage High on Arming
Low = Trigger Voltage Low on Arming
036 Bell Tst Arm No
Yes = Bell Test on Arming
No = No Bell Test on Arming
037 Bell Rbak Closing No
Yes = Bell Ringback at Closing
No = No Bell Ringback at Closing
038 Sound Rbak Yes
Yes = Keypad Ringback on all Signals
No = No Keypad Ringback
039 Fire Verification No
Yes = Relay 2 used as Fire Reset
No = Relay 2 not used for Smokes
040 Reset Key Yes
Yes = Reset by pressing 3 and 1
No = Only User Code Resets
041 Restore to Follow Loop No
Yes = All Rest Signals follow Loop
No = Restores after Bell Cutoff
042 Action on Abort No Abort
Abort Code (Sends Abort Code)
Stop Dialing (Kills Communicator)
No Abort
Restore (Transmits Restore Code)
043 Enable Keypad Commands Yes
Yes = User Commands Enabled
No = User Commands Disabled
044 Enable Zone Directory Yes
Yes = # 4 can scroll Zone Descriptions
No = No scrolling Zone Descriptions
045 Multi Part MD Yes
Yes = # 0 allows User to other Partitions
No = No User access to other Partitions
System Timing
Question Suggest Variable
046 Bell Delay 15S 00 00 (No Delay) to 15 x15 Seconds
Before Bell activation from Relay #1
047 Dialer Delay 15S 01 00 (No Delay) to 15 x15 Seconds
Before Dialer activation
048 Exit Del 15S 04 (60 seconds) 00 (None) to 15 x15 Seconds
049 Entry Del 1 15S 02 (30 seconds) 00 (None) to 15 x15 Seconds
050 Entry Del 2 15S 04 (60 seconds) 00 (None) to 15 x15 Seconds
051 CS Test Time 02 (02:00 AM) 00 to 24
052 AC Loss 15MN 04 (60 minutes) 00 (None) to 15 x15 Minutes
053 Exit Triggers NNNNNNNN (INSTANT/CODE moves Left/Right)
(0 toggles Y/N for each of 8 Triggers)
054 Entry Triggers NNNNNNNN (INSTANT/CODE moves Left/Right)
(0 toggles Y/N for each of 8 Triggers)
055 Timer1 1MN (Timeout Relay 1) 14 (14 minutes) 00 (None) to 15 x15 Minutes
056 Timer2 2MN (Timeout Relay 2) 15 (14 minutes) 00 (None) to 15 x15 Minutes
057 Timer3 3MN (Timeout Relay 3) 02 (14 minutes) 00 (None) to 15 x15 Minutes
058 Global Bell Lockout 15 00 to 15 Activations, 15 Disables
059 Local Bell Lockout 15 00 to 15 Activations, 15 Disables
060 Global Dialer Lockout 15 00 to 15 Activations, 15 Disables
061 Local Dialer Lockout 15 00 to 15 Activations, 15 Disables
System Fuction Codes
Question Suggest Variable
062 Bypass Code 0 0 to F, 0 = Default
063 Abort Code D 0 to F, D = Default
064 Opening Code 0 0 to F, B = Default
065 Closing Code 0 0 to F, C = Default
066 CS Test Code 00 00 to FF, 00 Disables
067 AC Loss Code 00 00 to FF, 00 Disables
068 AC Restore Code ? 0 to F, 0 Disables
069 Low Battery Code ? 0 to F, 0 Disables
070 Bat Restore Code ? 0 to F, 0 Disables
071 System Error Code ? 0 to F, 0 Disables
072 System Error Restore Code ? 0 to F, 0 Disables
073 Download Code EE 00 to FF, 00 Disables
074 Buzzer on AC Loss Yes Yes = Keypad Buzzer on AC Loss
No = No Buzzer on AC Loss
075 Buzzer on Low Battery Yes Yes = Keypad Buzzer on Low Battery
No = No Buzzer on Low Battery
076 Buzzer on System Error Yes Yes = Keypad Buzzer on System Error
No = No Buzzer on System Error
077 + – Ambush Enable No Yes = Ambush Code = User Code + – 1
No = Ambush Code is User 16
078 User 16 Ambush Code Yes Yes = User 16 Ambush Code
No = No Ambush Code
079 24 Hour AC Loss Yes Yes = Buzzer on AC Loss if Armed
No = No Buzzer on AC Loss if Armed
080 24 Hour Low Battery Yes Yes = Buzzer on Low Battery if Armed
No = No Buzzer on Low Battery if Armed
081 24 Hour System Error Yes Yes = Buzzer on System Error if Armed
No = No Buzzer on System Error if Armed
082 Trouble Type AC Loss 1 1 to 4, 1 = Default (see loc 100 to 110)
083 Trouble Type Low Battery 2 1 to 4, 2 = Default (see loc 100 to 110)
084 Trouble Type System Error 4 1 to 4, 4 = Default (see loc 100 to 110)
Alarm Types (These are not pre-defined that I know of, you must set them up)
Question Suggest Variable
085 Select Alarm Type 01 to 16, 00 = Skips
086 Description (enter Delay, Instant, Interior etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
087 CS Code ? 0 to F
088 CS Restore Code 0 0 to F
089 CS Reporting Path CS#1 Only CS#1 Only
CS#2 Only
CS#1 & CS#2
CS#1 BU CS#2 (CS2 as Backup)
CS#2 BU CS#1 (CS1 as Backup)
None (No Reports)
090 Bell Delay No Yes = Bell Delays per Location 046
No = No Bell Delay
091 Dialer Delay No Yes = Dialer Delays per Location 047
No = No Dialer Delay
092 Buzzer Enabled
(No if Silent Alarms & Holdup)
Yes Yes = Keypad Buzzer on Alarm
No = No Keypad Buzzer Delay
093 Display Alarm
(No if Silent Alarms & Holdup)
Yes Yes = Keypad Display on Alarm
No = No Keypad Display Delay
094 Timeout Selection ? 1 to 3 (see Timeouts in Loc 055 to 057)
095 Alarm Priority ? 01 (Highest) to 16 (Lowest)
Example: Fire, Duress = highest (16)
Burg would be next highest 15?
Supervisory orTroubles could be 14?
096 Momentary Triggers
(Triggers 1 to 8 )
NNNNNNNN (INSTANT/CODE moves Left/Right)
(0 toggles Y/N for each of 8 Triggers)
097 Latched Triggers
(Triggers 1-8)
NNNNNNNN (INSTANT/CODE moves Left/Right)
(0 toggles Y/N for each of 8 Triggers)
098 Relay 1 (Bell) Select NONE NONE (0 toggles selection)
PULSED
LATCHED
099 Relay 2 Select NONE
Trouble Types (Trouble Attributes)
Question Suggest Variable
100 Select Trouble Type 01 to 8, 0 = Skips to next Location
101 Description (enter Fire Trouble, Zone Trouble etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
102 CS Trouble Code ? 0 to F
103 CS Rep (Transmission Path) CS#1 Only CS#1 Only
CS#2 Only
CS#1 & CS#2
CS#1 BU CS#2 (CS2 as Backup)
CS#2 BU CS#1 (CS1 as Backup)
None (No Reports)
104 Dial Del (Trouble Dialer Delay) Yes Yes = Dialer Delay per Loc 047
No = No Dialer Delay
105 Bell Delay on Trouble Yes Yes = Bell Delay per Loc 044
106 Timeout Trouble ? 1 to 3 (see locations 055 to 057)
107 Mom Trg NNNNNNNN (INSTANT/CODE moves Left/Right)
(Which Trigger 1 to 8 is Momentary activated by Trouble) (0 toggles Y/N for each of 8 Triggers)
108 Lat Trg NNNNNNNN (INSTANT/CODE moves Left/Right)
(Which Trigger 1 to 8 is Maintained activated by Trouble) (0 toggles Y/N for each of 8 Triggers)
109 Relay 1 (Bell) Select NONE NONE (0 toggles selection)
PULSED
LATCHED
110 Relay 2 Select NONE
Zone Attributes
Question Suggest Variable
111 Select Zone 01 to 08, 00 Skips to next Location
09 to 16 if Zone Expander Used
112 Description (enter Living Room, Den, Hall, Front Door etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
113 CS Report Code 0 0 to F
114 Enable Bypassing
(Yes if Burg, No if Fire)
Yes Yes = User can bypass this Zone
No = User cannot bypass this Zone
115 CS Trouble Yes Yes = Report Zone Troubles
No = Do not report Zone Troubles
116 CS Restores (Alarms/Troubles) No Yes = Report Zone Restores
No = Don’t report Zone Restores
117 Partition ? 1 to 8 (1 if no partitions enabled)
118 Enable 24 Hour Zone No Yes = Zone is a 24 Hr Zone (Fire/Holdup)
No = Zone is a normal Zone
119 Enable 24 Hour Trouble No Yes = 24 Hour Zone Trouble (Fire)
No = Zone is a normal Zone
120 Alarm Type ? 01 to 16 (defined in Loc 85 to 99)
121 Trouble Type ? 1 to 8 (defined in loc 125 to 126)
122 Zone Type ? Perimeter (0 toggles options)
Entry/Exit
Interior EE Follower
Interior
123 Alarm on Open
(No for Smoke Detector)
Yes Yes = Alarm on Open Circuit
No = No Alarm on Open Circuit
124 Alarm on Short
(Keyswitch and Smoke Det)
Yes Yes = Alarm on Short Circuit
No = No Alarm on Short Circuit
125 Trouble on Open
(Yes for Smoke Detector)
No Yes = Trouble on Open Circuit
No = No Trouble on Open Circuit
126 Trouble on Short
(No for Smoke Detector)
No Yes = Trouble on Short Circuit
No = No Trouble on Short Circuit
127 Entry Delay
(only on E/E and Interior)
Delay 1 Delay 1 (0 toggles selection)
Delay 2
128 EN Lock (Swinger Shutdown) Yes Yes = Lockout (Specified in Loc 79 to 82)
No = No Bell/Dialer Lockout
129 CS Bypass (Bypass Reporting) No Yes = Will send Bypass Code to CS
No = Will not send Bypass Code to CS
130 Trouble Buzzer Yes Yes = Zone Troubles sound KP Buzzer
No = No KP Buzzer if Zone Trouble
131 Enable Chime ? Yes = Enable Chime for this Zone
No = No Chime for this Zone
132 Enable 750ms Response Yes Yes = Zone has 750ms Response
No = Zone has 250ms Response
133 Enable Keyswitch No Yes = Zone is a Keyswitch
No = Zone is not a Keyswitch
134 En Verif (Partition 1 only)
(Yes if Fire Zone)
No Yes = Fire Verification Enabled
No = Not Enabled
135 Silenced by Restore Yes Yes = Bell silenced by Restore Signal
No = Bell silenced by User Code
136 Pulse Count 15 (Disabled) 1 to 15 Minutes per activation
137 # Pulse 00 00 to 15 activations per period
Keypad Conditions
Question Suggest Variable
138 Select Keypad Type 0 = Skips
1 = * + # Alarm
2 = * + 1 Alarm
3 = 3 + # Alarm
4 = Duress Signal
139 CS Code 000 00 to 255, 000 Disables
140 Description (enter Fire Trouble, Zone Trouble etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
141 Alarm Type KP (Alarm Type) ? 01 to 16 (specified in Loc 085)
142 CS Rest No Yes = Sends Restore after Alarm
No = Doesn’t send Restore
Partitions
Question Suggest Variable
143 Select Partition 1 to 8, 0 = Skips
144 Keypad Partition YNNNNNNNYNNNNNNN    (INSTANT/CODE moves Left/Right)
(Keypads 1 to 8 are LED, 9 to 16 are LCD) (0 toggles Y/N for each of 8 Triggers)
145 Description Partition (enter Warehouse, Store Room, Apartment etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
Auto Upload (normally leave alone)
Question Suggest Variable
146 Auto Upload None None (0 toggles options)
Daily
Weekly
Monthly
147 Day of Month 01 01 to 31 Days
148 Day of Week Sunday Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
149 Report Hour 00 00 to 23
150 Report Minute 00 00 to 59
151 Mem Upload 99 00 to 99 Events
152 Auto Upload Account ???? 4-Digit Account Number to Identify
153 Auto Upload Description 1 (Enter whatever you want etc here)
INSTANT advances within a programming location
CODE moves backwards within a programming location
* 8 erases everything from cursor to end of field
7 scrolls letters for text questions
154 Auto Upload Description 2
155 Auto Upload Description 3
156 Auto Upload Description 4