DSC PC1555 Program

How To Identify Largest chip on main board will show
06000671 = 1555 v2.0
06000714 = 1555 v2.1
06000769 = 1555 v2.3 (will also say 2.30)
06000735 = Monitronics 1555 v2.0
Modules PC5132 Wireless Receiver
PC5400 Printer Module
Will not support PC5908/5928 Intercom or PC5580 Escort
Report Format SIA, Contact ID, 4/2, 3/1
Enter Program * 8 1555 (v2.0 & 2.1) or 5555 (v2.3)
Exit Program #
Move to location Enter 3-digit location, some areas may require # to exit
Default Panel 1. Power down then up, if board clicks panel is locked out (replace board)
2. If no clicks power back down and jumper from ZN 1 to PGM1, power up, wait 10 seconds
Enable Download * + 6 + Master Code + 5 (Enables for 6 hours)
(System also enables downloading for 1 hour if powered down then up)
Hex Program A = * 1 * B = * 2 * C = * 3 * D = * 4 * E = * 5 * F = * 6 *

[000] Keypad Assignment (must be done at each keypad)
[0] Slot (Valid entries 11 to 18 for Slot 1 to 8)
[1] Function Key 1 Assignment (Default = 03)
[2] Function Key 2 Assignment (Default = 04)
[3] Function Key 3 Assignment (Default = 06)
[4] Function Key 4 Assignment (Default = 14)
[5] Function Key 5 Assignment (Default = 16)
00 Null Key (Not Used) 08 * 1 Bypass Mode 16 * 0 Quick Exit
01 Not Used 09 * 2 Trouble Display 17 * 1 Reactivate Stay/Away’s
02 Not Used 10 * 3 Alarm Memory 18 Not Used
03 Stay Arm 11 * 5 User Programming 19 Not Used
04 Away Arm 12 * 6 User Functions 20 Not Used
05 * 9 No-Entry Arm 13 * 7 1 Utility Output 21 Not Used
06 * 4 Chime On/Off 14 * 7 2 Sensor Reset
07 * 6 4 System Test 15 Not Used
If multiple LCD keypads make one slot 8 to enable Zone description programming by downloader

[001] Zone 01-08 Definitions
Default Default
01 I_ _I_ _I Zone 01 05 I_ _I_ _I Zone 05
03 I_ _I_ _I Zone 02 05 I_ _I_ _I Zone 06
03 I_ _I_ _I Zone 03 05 I_ _I_ _I Zone 07
03 I_ _I_ _I Zone 04 05 I_ _I_ _I Zone 08
00 = Null Zone 09 = 24 Hr Supervisory (Links) 18 = 24hr Sprinkler
01 = Delay 1 10 = 24hr Supervisory Buzzer 19 = 24hr Water
02 = Delay 2 11 = 24hr Burglary 20 = 24hr Freeze
03 = Instant 12 = 24hr Holdup 21 = 24hr Latching Tamper
04 = Interior 13 = 24hr Gas 22 = Momentary Keyswitch Arm
05 = Interior Stay/Away 14 = 24hr Heat 23 = Maintained Keyswitch Arm
06 = Delay Stay/Away 15 = 24hr Medical 24 = Links Answer
07 = Delay 24hr Fire 16 = 24hr Panic 25 = Interior Delay (v2.3 only)
08 = Standard 24hr Fire 17 = 24 hr Emergency 87 = Delay Wireless Fire
88 = Standard Wireless Fire
[002] Zone 09-16 Zone Definitions (PC1555 v2.3 only)
Default Default
00 I_ _I_ _I Zone 09 00 I_ _I_ _I Zone 13
00 I_ _I_ _I Zone 10 00 I_ _I_ _I Zone 14
00 I_ _I_ _I Zone 11 00 I_ _I_ _I Zone 15
00 I_ _I_ _I Zone 12 00 I_ _I_ _I Zone 16

[003] Zone 17-24 Definitions (PC1555 v2.3 only)
Default Default
00 I_ _I_ _I Zone 17 00 I_ _I_ _I Zone 21
00 I_ _I_ _I Zone 18 00 I_ _I_ _I Zone 22
00 I_ _I_ _I Zone 19 00 I_ _I_ _I Zone 23
00 I_ _I_ _I Zone 20 00 I_ _I_ _I Zone 24

[004] Zone 25-32 Definitions (PC1555 v2.3 only)
Default Default
00 I_ _I_ _I Zone 25 00 I_ _I_ _I Zone 29
00 I_ _I_ _I Zone 26 00 I_ _I_ _I Zone 30
00 I_ _I_ _I Zone 27 00 I_ _I_ _I Zone 31
00 I_ _I_ _I Zone 28 00 I_ _I_ _I Zone 32

[005] System Times
Default
030 I_ _I_ _I_ _I Entry Delay 1 Enter 3 digits from [000-255]
045 I_ _I_ _I_ _I Entry Delay 2 Enter 3 digits from [000-255]
120 I_ _I_ _I_ _I Exit Delay Enter 3 digits from [000-255]
006 I_ _I_ _I_ _I Bell Cut-off Enter 3 digits from [000-255]
[006] Installer’s Code 1555 (v2.0 & 2.1) or 5555 (v2.3)
Default
1555 I_ _I_ _I_ _I_ _I

[007] Master Code
Default
1234 I_ _I_ _I_ _I_ _I

[008] Maintenance Code
Default
AAAA I_ _I_ _I_ _I_ _I

[009] PCS1555 PGM Output Programming (PGM 1 & 2)
Default
19 I_ _I_ _I PGM 01
10 I_ _I_ _I PGM 02
Programmable Output Options
00 = Not Used 11 = System Tamper
01 = Burg/Fire Bell Output 12 = TLM and Alarm
02 = For Future Use 13 = Kissoff Output
03 = Sensor Reset (4-wire Smokes *72) 14 = Ground Start Pulse
04 = 2-Wire Smokes (PGM2 ONLY)* 15 = Remote Operation (DLS-1)
05 = System (Parition) Armed Status 16 = Links 1000 Support (PGM1 only)
06 = Ready To Arm 17 = Away Armed Status
07 = Keypad Buzzer Follow Mode 18 = Stay Armed Status
08 = Courtesy Pulse 19 = [*] [7] [1] Command Output
09 = System Trouble Output 20 = [*] [7] [2] Command Output
10 = Latched System Event/Strobe 21 & 22 For Future Use
*For 2-Wire Smoke Support Jumper JP1 on board must be removed
(If Circuit Board has no JP1 jumper it cannot support a 2-Wire Smoke)
[012] Keypad Lockout Options
Default
000 I_0_I_0_I_0_I Number of Invalid Codes Before Lockout
000 I_0_I_0_I_0_I Lockout Duration (in minutes)

[013] First System Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
OFF I_OFF_I 1 Normally Closed Loops End-of-Line Resistors
OFF I_OFF_I 2 Double End-of-Line Resistors Single End-of-Line Resistors
ON I_ON_I 3 Panels shows trouble w/Armed Panel shows Fire Trbl only w/Armed
ON I_ON_I 4 Tamper/Fault do not show open Tampers/Fault show open
OFF I_OFF_I 5 Zone 1 is Fast Loop* Zone 1 is Standard Loop*
OFF I_OFF_I 6 Audible Exit Fault Enabled Audible Exit Fault Disabled
ON I_ON_I 7 Event Buffer follows Swinger Event Buf Logs Events Past swinger
OFF I_OFF_I 8 Temporal 3 Fire Signal Enabled Standard Pulsed Fire
*v2.0 & 2.1 only, v2.3 this is for Future Use

[014] Second System Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
OFF I_OFF_I 1 Arm/Disarm Bell Squawk enable Arm/Disarm Bell Squawk disable
OFF I_OFF_I 2 Bell Squawk During Auto Arm No Bell Squawk
ON I_ON_I 3 Bell Squawk On Exit Delay No Bell Squawk
OFF I_OFF_I 4 Bell Squawk On Entry Delay No Bell Squawk
OFF I_OFF_I 5 Bell Squawk On Trouble No Bell Squawk
ON I ON I 6 Audible Exit Beeps Silent Exit Delay
ON I_ON_I 7 Exit Delay Termination Enabled Exit Del. Termination Disabled
ON I_ON_I 8 Fire Bell is Continuous Fire Bell follows Bell Cut-Off

[015] Third System Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 [F] Keys Enabled Fire Keys Disabled
OFF I_ON_I 2 Panic Keys Audible Panic Keys Silent
OFF I_ON_I 3 Quick Exit Enabled Quick Exit Disabled
ON I_ON_I 4 Quick Arming Enabled Function Keys Disabled
OFF I_OFF_I 5 Code Required for Bypassing Code not Required
OFF I_OFF_I 6 Master Code Not Changable Master Code Changable
ON I_ON_I 7 TLM Enabled (Phone Monitor) TLM Disabled
OFF I_ON_I 8 TLM Audible When Armed TLM Trouble Only W/Armed

[016] Fourth System Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 AC Trouble Displayed AC Trouble not Displayed
OFF I_OFF_I 2 Trouble Flashes if AC Fails Trouble doesn’t follow AC
OFF I_OFF_I 3 Blank Keypad When Not Used Keypad always Active
OFF I_OFF_I 4 Code Req. to Stop KP Blanking No Code Required
OFF I_OFF_I 5 Keypad Backlight Enabled Keypad Backlighting Disabled
OFF I_OFF_I 6 Power Save Mode Enabled Power Save Mode Disabled
OFF I_OFF_I 7 Bypass Shows while Armed Bypass doesn’t show/Armed
OFF I_OFF_I 8 Keypad Tampers Enabled Keypad Tampers disabled

[017] Fifth System Option Code (v2.3 Only) (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 WLS Keyfob does not use Code WLS Keyfob uses Code
OFF I_OFF_I 2-7 For Future Use
OFF I_OFF_I 8 Bell Squawk Away Arm/Disarm Bell Squawk on all Arm/Disarm

[020] Keypad Zone Assignments (If using Z type keypads)
Default
00 I_ _I_ _I Keypad (Slot 1) Zone Valid entries are 01-08 (v2.0 & 2.1) 01-32 (v2.3)
00 I_ _I_ _I Keypad (Slot 2) Zone
00 I_ _I_ _I Keypad (Slot 3) Zone First assign keypad slot in 000 section 0 (11 to 18)
00 I_ _I_ _I Keypad (Slot 4) Zone (Keypad added as 11 would be Slot 1 here, 18 is Slot 8)
00 I_ _I_ _I Keypad (Slot 5) Zone then add Zone number here in proper slot
00 I_ _I_ _I Keypad (Slot 6) Zone (Ex: Zone 07 to Keypad 12 enter 00 07 00 00 00 00 00 00)
00 I_ _I_ _I Keypad (Slot 7) Zone (Keypad zones over-ride regular hardwire zones)
00 I_ _I_ _I Keypad (Slot 8) Zone Click HERE for Keypad Zone Wiring

Zone Attributes
Opt 1 Opt 2 Opt 3 Opt 4 Opt 5 Opt 6 Opt 7 Opt 8
ON Audible Steady Chime Bypass Force Swinger Tx Delay Wireless
OFF Silent Pulsed No No No No No No
[101] Zone 1 I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I
To
[132] Zone 32 I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I I_ _I
[160] Maximum Dialing Attempts to Each Phone Number
Default

008 I_ _I_ _I_ _I Valid entries are 001-255 attempts (Do not enter 000)

[161] Post Dial Wait for Handshake
Default

040 I_ _I_ _I_ _I Valid entries are 001-255 seconds

[202] Zone Assignments 1 to 8 (Toggle Zone lights ON or OFF then # to exit)
Default Option ON Option OFF
ON I_ON_I 1 Zone 1 is enabled Zone 1 is not enabled
ON I_ON_I 2 Zone 2 is enabled Zone 2 is not enabled
ON I_ON_I 3 Zone 3 is enabled Zone 3 is not enabled
ON I_ON_I 4 Zone 4 is enabled Zone 4 is not enabled
ON I_ON_I 5 Zone 5 is enabled Zone 5 is not enabled
ON I_ON_I 6 Zone 6 is enabled Zone 6 is not enabled
ON I_ON_I 7 Zone 7 is enabled Zone 7 is not enabled
ON I_ON_I 8 Zone 8 is enabled Zone 8 is not enabled

[203] Zone Assignments 9 to 16 (Toggle Zone lights ON or OFF then # to exit)
Default Option ON Option OFF   (PC1555 v2.3 only)
ON I_ON_I 1 Zone 9 is enabled Zone 09 is not enabled
ON I_ON_I 2 Zone 10 is enabled Zone 10 is not enabled
ON I_ON_I 3 Zone 11 is enabled Zone 11 is not enabled
ON I_ON_I 4 Zone 12 is enabled Zone 12 is not enabled
ON I_ON_I 5 Zone 13 is enabled Zone 13 is not enabled
ON I_ON_I 6 Zone 14 is enabled Zone 14 is not enabled
ON I_ON_I 7 Zone 15 is enabled Zone 15 is not enabled
ON I_ON_I 8 Zone 16 is enabled Zone 16 is not enabled

[204] Zone Assignments 17 to 24 (Toggle Zone lights ON or OFF then # to exit)
Default Option ON Option OFF   (PC1555 v2.3 only)
ON I_ON_I 1 Zone 17 is enabled Zone 17 is not enabled
ON I_ON_I 2 Zone 18 is enabled Zone 18 is not enabled
ON I_ON_I 3 Zone 19 is enabled Zone 19 is not enabled
ON I_ON_I 4 Zone 20 is enabled Zone 20 is not enabled
ON I_ON_I 5 Zone 21 is enabled Zone 21 is not enabled
ON I_ON_I 6 Zone 22 is enabled Zone 22 is not enabled
ON I_ON_I 7 Zone 23 is enabled Zone 23 is not enabled
ON I_ON_I 8 Zone 24 is enabled Zone 24 is not enabled

[205] Zone Assignments 25 to 32 (Toggle Zone lights ON or OFF then # to exit)
Default Option ON Option OFF   (PC1555 v2.3 only)
ON I_ON_I 1 Zone 25 is enabled Zone 25 is not enabled
ON I_ON_I 2 Zone 26 is enabled Zone 26 is not enabled
ON I_ON_I 3 Zone 27 is enabled Zone 27 is not enabled
ON I_ON_I 4 Zone 28 is enabled Zone 28 is not enabled
ON I_ON_I 5 Zone 29 is enabled Zone 29 is not enabled
ON I_ON_I 6 Zone 30 is enabled Zone 30 is not enabled
ON I_ON_I 7 Zone 31 is enabled Zone 31 is not enabled
ON I_ON_I 8 Zone 32 is enabled Zone 32 is not enabled

Communicator Programming

[301] First Telephone Number (32 Digits)
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
*2 = * *3 = # *4 = Wait for Dial Tone *5 = 2 Sec Pause *6 = End Number
(If adding more than one hex digit Example: *555* gives 3 2-second pauses)

[302] Second Telephone Number
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
Program Pager number + pauses *5555* gives 4 2-second pauses, uses 1st Account #
Monitronics PC1555’s with burned in 1st & 2nd Numbers cannot do pagers
Monitronics PC1555’s with burned in 1st & 3rd Numbers can do pagers

[303] Third Telephone Number (32 Digits)
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I

[310] First/Third Receiver Telephone Account Code (4 Digits)
I_ _I_ _I_ _I_ _I
If SIA enter 0 if any 0 in Account Number
If 4/2 or Contact ID use *1* for any 0 in Account Number
Pager will not send properly if Hex Characters A C D F are in Account Number

[311] Second Receiver Telephone Account Code (4 Digits)
I_ _I_ _I_ _I_ _I

[320] Alarm Report Codes Zone 01 to 08
Default Default
FF I_1_I_1_I Zone 01 Alarm FF I_1_I_1_I Zone 05 Alarm
FF I_1_I_1_I Zone 02 Alarm FF I_1_I_1_I Zone 06 Alarm
FF I_1_I_1_I Zone 03 Alarm FF I_1_I_1_I Zone 07 Alarm
FF I_1_I_1_I Zone 04 Alarm FF I_1_I_1_I Zone 08 Alarm

[321] Alarm Report Codes Zone 09 to 16 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 09 Alarm FF I_F_I_F_I Zone 13 Alarm
FF I_F_I_F_I Zone 10 Alarm FF I_F_I_F_I Zone 14 Alarm
FF I_F_I_F_I Zone 11 Alarm FF I_F_I_F_I Zone 15 Alarm
FF I_F_I_F_I Zone 12 Alarm FF I_F_I_F_I Zone 16 Alarm

[322] Alarm Report Codes Zone 17 to 24 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 17 Alarm FF I_F_I_F_I Zone 21 Alarm
FF I_F_I_F_I Zone 18 Alarm FF I_F_I_F_I Zone 22 Alarm
FF I_F_I_F_I Zone 19 Alarm FF I_F_I_F_I Zone 23 Alarm
FF I_F_I_F_I Zone 20 Alarm FF I_F_I_F_I Zone 24 Alarm

[323] Alarm Report Codes Zone 25 to 32 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 25 Alarm FF I_F_I_F_I Zone 29 Alarm
FF I_F_I_F_I Zone 26 Alarm FF I_F_I_F_I Zone 30 Alarm
FF I_F_I_F_I Zone 27 Alarm FF I_F_I_F_I Zone 31 Alarm
FF I_F_I_F_I Zone 28 Alarm FF I_F_I_F_I Zone 32 Alarm

[324] Alarm Restoral Report Codes Zones 01 to 08
Default Default
FF I_F_I_F_I Zone 01 Restoral FF I_F_I_F_I Zone 05 Restoral
FF I_F_I_F_I Zone 02 Restoral FF I_F_I_F_I Zone 06 Restoral
FF I_F_I_F_I Zone 03 Restoral FF I_F_I_F_I Zone 07 Restoral
FF I_F_I_F_I Zone 04 Restoral FF I_F_I_F_I Zone 08 Restoral

[325] Alarm Restoral Report Codes Zone 09 to 16 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 09 Restoral FF I_F_I_F_I Zone 13 Restoral
FF I_F_I_F_I Zone 10 Restoral FF I_F_I_F_I Zone 14 Restoral
FF I_F_I_F_I Zone 11 Restoral FF I_F_I_F_I Zone 15 Restoral
FF I_F_I_F_I Zone 12 Restoral FF I_F_I_F_I Zone 16 Restoral

[326] Alarm Restoral Report Codes Zone 17 to 24 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 17 Restoral FF I_F_I_F_I Zone 21 Restoral
FF I_F_I_F_I Zone 18 Restoral FF I_F_I_F_I Zone 22 Restoral
FF I_F_I_F_I Zone 19 Restoral FF I_F_I_F_I Zone 23 Restoral
FF I_F_I_F_I Zone 20 Restoral FF I_F_I_F_I Zone 24 Restoral

[327] Alarm Restoral Report Codes Zone 25 to 32 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 25 Restoral FF I_F_I_F_I Zone 29 Restoral
FF I_F_I_F_I Zone 26 Restoral FF I_F_I_F_I Zone 30 Restoral
FF I_F_I_F_I Zone 27 Restoral FF I_F_I_F_I Zone 31 Restoral
FF I_F_I_F_I Zone 28 Restoral FF I_F_I_F_I Zone 32 Restoral

[328] Miscellaneous Alarm Reporting Codes
Default Default
FF I_1_I_1_I Duress FF I_F_I_F_I Zone Expander Supervisory Alarm
FF I_1_I_1_I Opening After Alarm (Cancel) FF I_F_I_F_I Zone Expander Supervisory Restore
FF I_1_I_1_I Recent Closing (Exit Alarm) FF I_F_I_F_I Cross Zone Police Alarm

[329] Priority Alarm and Restoral
Default Default
FF I_1_I_1_I Keypad Fire Alarm FF I_0_I_0_I Keypad Fire Restoral
FF I_1_I_1_I Keypad Aux (Medical) Alarm FF I_0_I_0_I Keypad Aux (Medical) Restoral
FF I_1_I_1_I Keypad Panic Alarm FF I_0_I_0_I Keypad Panic Alarm
FF I_0_I_0_I PGM2 Alarm (11 if 2-wire smoke) FF I_0_I_0_I PGM2 Restoral (11 if 2-wire smoke)

[330] Tamper Reporting Codes Zones 01 to 08
Default Default
FF I_F_I_F_I Zone 01 Tamper FF I_F_I_F_I Zone 05 Tamper
FF I_F_I_F_I Zone 02 Tamper FF I_F_I_F_I Zone 06 Tamper
FF I_F_I_F_I Zone 03 Tamper FF I_F_I_F_I Zone 07 Tamper
FF I_F_I_F_I Zone 04 Tamper FF I_F_I_F_I Zone 08 Tamper

[331] Tamper Report Codes Zone 09 to 16 (PC580 v2.3 only)
Default Default
FF I_F_I_F_I Zone 09 Tamper FF I_F_I_F_I Zone 13 Tamper
FF I_F_I_F_I Zone 10 Tamper FF I_F_I_F_I Zone 14 Tamper
FF I_F_I_F_I Zone 11 Tamper FF I_F_I_F_I Zone 15 Tamper
FF I_F_I_F_I Zone 12 Tamper FF I_F_I_F_I Zone 16 Tamper

[332] Tamper Report Codes Zone 17 to 24 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 17 Tamper FF I_F_I_F_I Zone 21 Tamper
FF I_F_I_F_I Zone 18 Tamper FF I_F_I_F_I Zone 22 Tamper
FF I_F_I_F_I Zone 19 Tamper FF I_F_I_F_I Zone 23 Tamper
FF I_F_I_F_I Zone 20 Tamper FF I_F_I_F_I Zone 24 Tamper

[333] Tamper Report Codes Zone 25 to 32 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 25 Tamper FF I_F_I_F_I Zone 29 Tamper
FF I_F_I_F_I Zone 26 Tamper FF I_F_I_F_I Zone 30 Tamper
FF I_F_I_F_I Zone 27 Tamper FF I_F_I_F_I Zone 31 Tamper
FF I_F_I_F_I Zone 28 Tamper FF I_F_I_F_I Zone 32 Tamper

[334] Tamper Restoral Reporting Codes Zones 01 to 08
Default Default
FF I_F_I_F_I Zone 01 Tamper Restoral FF I_F_I_F_I Zone 05 Tamper Restoral
FF I_F_I_F_I Zone 02 Tamper Restoral FF I_F_I_F_I Zone 06 Tamper Restoral
FF I_F_I_F_I Zone 03 Tamper Restoral FF I_F_I_F_I Zone 07 Tamper Restoral
FF I_F_I_F_I Zone 04 Tamper Restoral FF I_F_I_F_I Zone 08 Tamper Restoral

[335] Tamper Restoral Report Codes Zone 09 to 16 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 09 Tamper Restoral FF I_F_I_F_I Zone 13 Tamper Restoral
FF I_F_I_F_I Zone 10 Tamper Restoral FF I_F_I_F_I Zone 14 Tamper Restoral
FF I_F_I_F_I Zone 11 Tamper Restoral FF I_F_I_F_I Zone 15 Tamper Restoral
FF I_F_I_F_I Zone 12 Tamper Restoral FF I_F_I_F_I Zone 16 Tamper Restoral

[336] Tamper Restoral Report Codes Zone 17 to 24 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 17 Tamper Restoral FF I_F_I_F_I Zone 21 Tamper Restoral
FF I_F_I_F_I Zone 18 Tamper Restoral FF I_F_I_F_I Zone 22 Tamper Restoral
FF I_F_I_F_I Zone 19 Tamper Restoral FF I_F_I_F_I Zone 23 Tamper Restoral
FF I_F_I_F_I Zone 20 Tamper Restoral FF I_F_I_F_I Zone 24 Tamper Restoral

[337] Tamper Restoral Report Codes Zone 25 to 32 (PC1555 v2.3 only)
Default Default
FF I_F_I_F_I Zone 25 Tamper Restoral FF I_F_I_F_I Zone 29 Tamper Restoral
FF I_F_I_F_I Zone 26 Tamper Restoral FF I_F_I_F_I Zone 30 Tamper Restoral
FF I_F_I_F_I Zone 27 Tamper Restoral FF I_F_I_F_I Zone 31 Tamper Restoral
FF I_F_I_F_I Zone 28 Tamper Restoral FF I_F_I_F_I Zone 32 Tamper Restoral

[338] Miscellaneous Tamper Reporting Codes
Default
FF I_F_I_F_I General System Tamper
FF I_F_I_F_I General System Tamper Restoral
FF I_F_I_F_I Keypad Lockout

[339] Closing (Arming) Reporting Codes Access Codes 01 to 08
Default Default
FF I_F_I_F_I User Code 01 Closing FF I_F_I_F_I User Code 05 Closing
FF I_F_I_F_I User Code 02 Closing FF I_F_I_F_I User Code 06 Closing
FF I_F_I_F_I User Code 03 Closing FF I_F_I_F_I User Code 07 Closing
FF I_F_I_F_I User Code 04 Closing FF I_F_I_F_I User Code 08 Closing

[340] Closing (Arming) Reporting Codes Access Codes 09 to 16
Default Default
FF I_F_I_F_I User Code 09 Closing FF I_F_I_F_I User Code 13 Closing
FF I_F_I_F_I User Code 10 Closing FF I_F_I_F_I User Code 14 Closing
FF I_F_I_F_I User Code 11 Closing FF I_F_I_F_I User Code 15 Closing
FF I_F_I_F_I User Code 12 Closing FF I_F_I_F_I User Code 16 Closing

[341] Closing (Arming) Reporting Codes Access Codes 17 to 24
Default Default
FF I_F_I_F_I User Code 17 Closing FF I_F_I_F_I User Code 21 Closing
FF I_F_I_F_I User Code 18 Closing FF I_F_I_F_I User Code 22 Closing
FF I_F_I_F_I User Code 19 Closing FF I_F_I_F_I User Code 23 Closing
FF I_F_I_F_I User Code 20 Closing FF I_F_I_F_I User Code 24 Closing

[342] Closing (Arming) Reporting Codes Access Codes 25 to 32
Default Default
FF I_F_I_F_I User Code 25 Closing FF I_F_I_F_I User Code 29 Closing
FF I_F_I_F_I User Code 26 Closing FF I_F_I_F_I User Code 30 Closing
FF I_F_I_F_I User Code 27 Closing FF I_F_I_F_I User Code 31 Closing
FF I_F_I_F_I User Code 28 Closing FF I_F_I_F_I User Code 32 Closing

[343] Miscellaneous Closing (Arming) Reporting Codes
Default Default
FF I_F_I_F_I User Code 33 Closing FF I_F_I_F_I Master Code 42 Closing
FF I_F_I_F_I User Code 34 Closing FF I_F_I_F_I Partial Closing
FF I_F_I_F_I Master Code 40 Closing FF I_F_I_F_I Special Closing
FF I_F_I_F_I Master Code 41 Closing

[344] Opening (Disarming) Reporting Codes Access Codes 01 to 08
Default Default
FF I_F_I_F_I User Code 01 Opening FF I_F_I_F_I User Code 05 Opening
FF I_F_I_F_I User Code 02 Opening FF I_F_I_F_I User Code 06 Opening
FF I_F_I_F_I User Code 03 Opening FF I_F_I_F_I User Code 07 Opening
FF I_F_I_F_I User Code 04 Opening FF I_F_I_F_I User Code 08 Opening

[345] Opening (Disarming) Reporting Codes Access Codes 09 to 16
Default Default
FF I_F_I_F_I User Code 09 Opening FF I_F_I_F_I User Code 13 Opening
FF I_F_I_F_I User Code 10 Opening FF I_F_I_F_I User Code 14 Opening
FF I_F_I_F_I User Code 11 Opening FF I_F_I_F_I User Code 15 Opening
FF I_F_I_F_I User Code 12 Opening FF I_F_I_F_I User Code 16 Opening

[346] Opening (Disarming) Reporting Codes Access Codes 17 to 24
Default Default
FF I_F_I_F_I User Code 17 Opening FF I_F_I_F_I User Code 21 Opening
FF I_F_I_F_I User Code 18 Opening FF I_F_I_F_I User Code 22 Opening
FF I_F_I_F_I User Code 19 Opening FF I_F_I_F_I User Code 23 Opening
FF I_F_I_F_I User Code 20 Opening FF I_F_I_F_I User Code 24 Opening

[347] Opening (Disarming) Reporting Codes Access Codes 25 to 32
Default Default
FF I_F_I_F_I User Code 25 Opening FF I_F_I_F_I User Code 29 Opening
FF I_F_I_F_I User Code 26 Opening FF I_F_I_F_I User Code 30 Opening
FF I_F_I_F_I User Code 27 Opening FF I_F_I_F_I User Code 31 Opening
FF I_F_I_F_I User Code 28 Opening FF I_F_I_F_I User Code 32 Opening

[348] Miscellaneous Opening (Disarming) Reporting Codes
Default Default
FF I_F_I_F_I User Code 33 Opening FF I_F_I_F_I Master Code 42 Opening
FF I_F_I_F_I User Code 34 Opening FF I_F_I_F_I Auto Arm Cancellation
FF I_F_I_F_I Master Code 40 Opening FF I_F_I_F_I Special Opening
FF I_F_I_F_I Master Code 41 Opening

[349] Maintenance Alarm Reporting Codes
Default Default
FF I_1_I_1_I Battery Trouble FF I_0_I_0_I Auxiliary Power Supply Trouble
FF I_1_I_1_I AC Failure Trouble FF I_0_I_0_I TLM Trouble (via LINKS)
FF I_1_I_1_I Bell Circuit Trouble FF I_0_I_0_I For Future Use
FF I_1_I_1_I Fire Trouble Alarm FF I_0_I_0_I General System Supervisory

[350] Maintenance Restoral Reporting Codes
Default Default
FF I_1_I_1_I Battery Trouble Restoral FF I_0_I_0_I Auxiliary Power Supply Restoral
FF I_1_I_1_I AC Failure Trouble Restoral FF I_1_I_1_I TLM Trouble Restoral
FF I_1_I_1_I Bell Circuit Trouble Restoral FF I_0_I_0_I For Future Use
FF I_1_I_1_I Fire Trouble Alarm Restoral FF I_0_I_0_I General System Superv. Restoral

[351] Miscellaneous Maintenance Report Codes
Default Default
FF I_1_I_1_I Phone Number 1 FTC FF I_0_I_0_I DLS Lead OUT
FF I_1_I_1_I Phone Number 1 FTC Restoral FF I_0_I_0_I Zone Fault Alarm
FF I_0_I_0_I Event Buffer 75% Full FF I_0_I_0_I Zone Fault Restoral
FF I_0_I_0_I DLS Lead IN FF I_0_I_0_I Delinquency Code

[352] Test Transmission Report Codes
Default Default
FF I_1_I_1_I Periodic Test FF I_0_I_0_I LINKS 1000 Test Transmission Code
FF I_1_I_1_I System Test

[353] Wireless Maintenance Report Codes
Default
FF I_1_I_1_I General Zone Low Battery
FF I_1_I_1_I General Zone Low Battery Restoral

[360] Communicator Format Options
Default
02 I_0_I_4_I 1st & 3rd Phone
01 = 4/2 20BPS 1400HZ 04 = SIA FSK
02 = 4/2 20BPS 2300HZ 05 = Pager
03 = Contact ID 06 = Residential Dial (v2.3 only)
02 I_0_I_4_I 2nd Phone Number

[361] Alarms and Restorals Call Directions (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 1st Telephone Number Disabled
OFF I_OFF_I 2 2nd Telephone Number Disabled
OFF I_OFF_I 3 1st Telphone Number (LINKS) Disabled
OFF I_OFF_I 4 2nd Telephone Number (LINKS) Disabled
OFF I_OFF_I 5 to 8 for Future Use

[363] Tampers & Restorals Call Directions (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 1st Telephone Number Disabled
OFF I_OFF_I 2 2nd Telephone Number Disabled
OFF I_OFF_I 3 1st Telphone Number (LINKS) Disabled
OFF I_OFF_I 4 2nd Telephone Number (LINKS) Disabled
OFF I_OFF_I 5 to 8 for Future Use

[365] Openings & Closings Call Directions (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_OFF_I 1 1st Telephone Number Disabled
OFF I_OFF_I 2 2nd Telephone Number Disabled
OFF I_OFF_I 3 1st Telphone Number (LINKS) Disabled
OFF I_OFF_I 4 2nd Telephone Number (LINKS) Disabled
OFF I_OFF_I 5 to 8 for Future Use

[367] Maintenance Alarms & Restorals (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 1st Telephone Number Disabled
OFF I_OFF_I 2 2nd Telephone Number Disabled
OFF I_OFF_I 3 1st Telphone Number (LINKS) Disabled
OFF I_OFF_I 4 2nd Telephone Number (LINKS) Disabled
OFF I_OFF_I 5 to 8 for Future Use

[368] Test Transmissions Call Directions (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 1st Telephone Number Disabled
OFF I_OFF_I 2 2nd Telephone Number Disabled
OFF I_OFF_I 3 1st Telphone Number (LINKS) Disabled
OFF I_OFF_I 4 2nd Telephone Number (LINKS) Disabled
OFF I_OFF_I 5 to 8 for Future Use

[370] Communication Variables
Default
003 I_0_I_0_I_3_I Swinger Shutdwn (Alarms&Rest) (001-014 Trans, 000=disabled)
003 I_0_I_0_I_3_I Swinger Shutdwn (Tampers&Rest) (001-014 Trans, 000=disabled)
003 I_0_I_0_I_3_I Swinger Shutdwn (Maint&Rest) (001-014 Trans, 000=disabled)
000 I_0_I_0_I_0_I Communication Delay (001-255 seconds)
030 I_0_I_6_I_0_I AC Failure Communication Delay (001-255 minutes)
003 I_0_I_0_I_6_I TLM Trouble Delay Land Line (No. of valid checks required – 000-255 x 10s)
030 I_0_I_3_I_0_I TLM Trouble Delay Links (No. of valid checks required – 000-255 x 10s)
030 I_0_I_2_I_8_I Test Transmission Cycle (001-255 days; 000 to disable)
007 I_0_I_0_I_7_I Transmitter Low Batt Delay (000-255 days)
030 I_0_I_3_I_0_I Delinquency Transmission Cycle (000-255 days)

[371] Test Transmission Time of Day
Default
9999 I_0_I_2_I_0_I_0_I   Valid entries are 0000 to 2359

[380] First Communicator Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
ON I_ON_I 1 Communications Enabled Disabled
OFF I_ON_I 2 Restorals on Bell Time-Out Restorals Follow Zones
OFF I_OFF_I 3 Pulse Dialing DTMF Dialing
ON I_ON_I 4 Switch to Pulse after 5th Attempt DTMF for All Attempts
OFF I_OFF_I 5 3rd Phone Number Enabled Disabled
OFF I_OFF_I 6 Alternate Dial 1st & 3rd Call 1st Number, Backup to 3rd
(Monitronics) 6 Dial 1st Phone Number Dial 3rd Phone Number
OFF I_OFF_I 7 Call Links as well as Land Line Links is Backup to Land Line
OFF I_OFF_I 8 Delinquency Follows Activity (Hrs) Delinquency Follows Arming (Days)

Monitronics 1555 Information
If Phone 1 & 2 are preprogrammed set Lights 1 & 4 ON, all others OFF
If Phone 1 & 3 are preprogrammed set Lights 1, 4 and 6 ON, all others OFF

[381] Second Communicator Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
OFF I_OFF_I 1 Open after Alarm Ringback Enable Disabled
OFF I_OFF_I 2 Open After Bell Ringback Enable Disabled
OFF I_OFF_I 3 SIA sends Programmed Report Codes SIA sends Automatic Report Codes
OFF I_OFF_I 4 Closing Confirmation Enabled Disabled
ON I_ON_I 5 For Future Use
OFF I_OFF_I 6 For Future Use
ON I_OFF_I 7 Contact ID uses Pgrm’d Report Codes* Contact ID sends Automatic Reports*
OFF I_OFF_I 8 For Future Use
* = Version 2.1 & 2.3 only

[390] Links Preamble First Telephone Number
Default
FFFF I_ _I_ _I_ _I_ _I

[391] Links Preamble Second Telephone Number
Default
FFFF I_ _I_ _I_ _I_ _I

[392] Links Preamble Third Telephone Number
Default
FFFF I_ _I_ _I_ _I_ _I

[393] Links Special Function Preamble
Default
FFFF I_ _I_ _I_ _I_ _I

Download Programming

[401] First Downloading Option Code (Toggle Zone lights ON or OFF then # to exit)
Default Option ON OFF
OFF I_ON_I 1 Downloading Enabled Disabled
ON I_ON_I 2 User Can Enable DLS Window Disabled
OFF I_OFF_I 3 Call Back Enabled Disabled
OFF I_OFF_I 4 User Initiated Call-Up Enabled Disabled
OFF I_OFF_I 5 to 8 For Future Use

[402] Downloading Telephone Number (32 Digits)
I_1_I_8_I_0_I_0_I_3_I_5_I_8_I_6_I_7_I_2_I_5_I_ _I_ _I_ _I_ _I_ _I_ _I_ _I

[403] Downloading Access Code
Default
1555 I_9_I_5_I_2_I_4_I

[404] Panel Identification Code
Default
1555 I_1_I_5_I_5_I_5_I

[405] Answer Machine Double Call Timer
Default
060 I_0_I_6_I_0_I

[406] Number of Rings to Answer On
Default
000 I_0_I_1_I_0_I

[490] Links Preamble Download Phone Number
Default
FFFF I_F_I_F_I_F_I_F_I

[499] Installer Code + [499] Initiate PC-Link (Local Downloading)

[701] First International Options Code (v2.3 only)
Default Option ON OFF
OFF I_ _I 1 to 4 For Future Use
OFF I_ _I 5 6-Digit User Access Codes 4-Digit User Access Codes
OFF I_ _I 6 Busy Tone Detection Enabled Disabled
OFF I_ _I 7 to 8 For Future Use

Module Programming

[801] PC5400 Printer Module

[803] PC2150/2250 Long Range Radio or Skyroute

[804] PC5132 Wireless Receiver (Use “ESN” Number from sticker on sensor, if only “SN” add 0 as 1st digit)

PC5132 v3.x and below use 900Mhz sensors PC5132 v4.x and above use 433Mhz sensors
All DSC Wireless sensor Serial Numbers go here EXCEPT
WLS910 Hand Held Keypad (see section 33 to 36)
WLS909 Keyfob (see section 41 to 56)

Default = 000000   (WARNING! If these sections only accept 5 digits Receiver is V2.0 or 2.1!)
[01] Zone 01 I_ _I_ _I_ _I_ _I_ _I_ _I [17] Zone 17 I_ _I_ _I_ _I_ _I_ _I_ _I
[02] Zone 02 I_ _I_ _I_ _I_ _I_ _I_ _I [18] Zone 18 I_ _I_ _I_ _I_ _I_ _I_ _I
[03] Zone 03 I_ _I_ _I_ _I_ _I_ _I_ _I [19] Zone 19 I_ _I_ _I_ _I_ _I_ _I_ _I
[04] Zone 04 I_ _I_ _I_ _I_ _I_ _I_ _I [20] Zone 20 I_ _I_ _I_ _I_ _I_ _I_ _I
[05] Zone 05 I_ _I_ _I_ _I_ _I_ _I_ _I [21] Zone 21 I_ _I_ _I_ _I_ _I_ _I_ _I
[06] Zone 06 I_ _I_ _I_ _I_ _I_ _I_ _I [22] Zone 22 I_ _I_ _I_ _I_ _I_ _I_ _I
[07] Zone 07 I_ _I_ _I_ _I_ _I_ _I_ _I [23] Zone 23 I_ _I_ _I_ _I_ _I_ _I_ _I
[08] Zone 08 I_ _I_ _I_ _I_ _I_ _I_ _I [24] Zone 24 I_ _I_ _I_ _I_ _I_ _I_ _I
[09] Zone 09 I_ _I_ _I_ _I_ _I_ _I_ _I [25] Zone 25 I_ _I_ _I_ _I_ _I_ _I_ _I
[10] Zone 10 I_ _I_ _I_ _I_ _I_ _I_ _I [26] Zone 26 I_ _I_ _I_ _I_ _I_ _I_ _I
[11] Zone 11 I_ _I_ _I_ _I_ _I_ _I_ _I [27] Zone 27 I_ _I_ _I_ _I_ _I_ _I_ _I
[12] Zone 12 I_ _I_ _I_ _I_ _I_ _I_ _I [28] Zone 28 I_ _I_ _I_ _I_ _I_ _I_ _I
[13] Zone 13 I_ _I_ _I_ _I_ _I_ _I_ _I [29] Zone 29 I_ _I_ _I_ _I_ _I_ _I_ _I
[14] Zone 14 I_ _I_ _I_ _I_ _I_ _I_ _I [30] Zone 30 I_ _I_ _I_ _I_ _I_ _I_ _I
[15] Zone 15 I_ _I_ _I_ _I_ _I_ _I_ _I [31] Zone 31 I_ _I_ _I_ _I_ _I_ _I_ _I
[16] Zone 16 I_ _I_ _I_ _I_ _I_ _I_ _I [32] Zone 32 I_ _I_ _I_ _I_ _I_ _I_ _I

Handheld Keypad Serial Numbers
Default = 000000
[33] Keypad 01 I_ _I_ _I_ _I_ _I_ _I_ _I [35] Keypad 03 I_ _I_ _I_ _I_ _I_ _I_ _I
[34] Keypad 02 I_ _I_ _I_ _I_ _I_ _I_ _I [36] Keypad 04 I_ _I_ _I_ _I_ _I_ _I_ _I

Wireless Keyfob Serial Numbers
Default = 000000
[41] Key 01 I_ _I_ _I_ _I_ _I_ _I_ _I [49] Key 09 I_ _I_ _I_ _I_ _I_ _I_ _I
[42] Key 02 I_ _I_ _I_ _I_ _I_ _I_ _I [50] Key 10 I_ _I_ _I_ _I_ _I_ _I_ _I
[43] Key 03 I_ _I_ _I_ _I_ _I_ _I_ _I [51] Key 11 I_ _I_ _I_ _I_ _I_ _I_ _I
[44] Key 04 I_ _I_ _I_ _I_ _I_ _I_ _I [52] Key 12 I_ _I_ _I_ _I_ _I_ _I_ _I
[45] Key 05 I_ _I_ _I_ _I_ _I_ _I_ _I [53] Key 13 I_ _I_ _I_ _I_ _I_ _I_ _I
[46] Key 06 I_ _I_ _I_ _I_ _I_ _I_ _I [54] Key 14 I_ _I_ _I_ _I_ _I_ _I_ _I
[47] Key 07 I_ _I_ _I_ _I_ _I_ _I_ _I [55] Key 15 I_ _I_ _I_ _I_ _I_ _I_ _I
[48] Key 08 I_ _I_ _I_ _I_ _I_ _I_ _I [56] Key 16 I_ _I_ _I_ _I_ _I_ _I_ _I

Handheld Keypad and Options
Handheld Keypad Options   (WLS910 Hand Held Keypad Button Definitions here)
[57] Function Key 1 I_ _I_ _I Function Key 3 I_ _I_ _I
Function Key 2 I_ _I_ _I Function Key 4 I_ _I_ _I

Wireless Keyfob
Wireless Key Options   (WLS909 Keyfob Button Definitions here)
[59] Function Key 1 I_ _I_ _I Function Key 3 I_ _I_ _I
Function Key 2 I_ _I_ _I Function Key 4 I_ _I_ _I
[00] Key Not Used [16] * 0 Quick Exit
[01] For Future Use [17] * 1 Reactivate Stay/Aways
[02] For Future Use [18] For Future Use
[03] Stay Arm [19] * 7 3 Command Output 3
[04] Away Arm [20] For Future Use
[05] * 9 No-Entry Arm [21] * 7 4 Command Output 4
[06] * 4 Chime ON/OFFl [22] to [26] For Future Use
[07] * 6 —- 4 System Test [27] Disarm (OFF)
[08] to [12] For Future Use [28] Fire Alarm
[13] * 7 1 Command Output 1 [29] Aux/Medical Alarm
[14] * 7 2 Sensor Reset [30] Police Panic
[15] For Future Use
Special Installer Functions
[981] Installer Buzzer Walk Test Mode Begin/End
[902] Module Supervision Enable/Reset
[903] View Module Supervision Field

[904] Wireless Module Placement Test
Select the module / transmitter (Zones 01-32).
Press # to Cancel.
Placement Led Keypad Alpha Keypad Bell / Buzzer

Good Light 1 ON Steady GOOD 1 Beep / Squawk
Fair Light 2 ON Steady FAIR 2 Beeps / Squawks
Bad Light 3 ON Steady BAD 3 Beeps / Squawks
[990] Installer Lockout Enable

[991] Installer Lockout Disable

[993] Restore Links Long Range Radio Default Programming 993 + Installer Code + 993

[996] Restore PC5132 Default Programming 996 + Installer Code + 996

[997] Restore PC5400 Default Programming 997 + Installer Code + 997

[999] Restore PC1555 Default Programming 999 + Installer Code + 999

LCD Keypad Programming