1. |
|
Globals |
|
Variables/Defaults |
|
1.1 |
Tbl |
I_F_I |
0 to 9, B to F, Blank Blank = No Report
F is automatic if BFSK or Modem II used
|
|
1.2 |
Res |
I_ _I |
0 to 9, B to F, Blank Blank = No Report
E is automatic if BFSK or Modem II used
|
|
1.3 |
Open |
I_ _I |
0 to 9, B to F, Blank Blank = No Report
F is automatic if BFSK or Modem II used
|
|
1.4 |
Close |
I_ _I |
0 to 9, B to F, Blank Blank = No Report
F is automatic if BFSK or Modem II used
|
|
1.5 |
Cancel |
I_ _I |
0 to 9, B to F, Blank Blank = No Report
F is automatic if BFSK or Modem II used
|
|
1.6 |
Duress |
I_D_I |
0 to 9, B to F, Blank Blank = No Report
D is automatic if BFSK or Modem II used
|
|
1.7 |
BatSupv |
I_ _I |
0 to 9, B to F, Blank Blank = No Report
If needed use 9 (Trouble Zone 9)
|
|
1.8 |
Bell (timeout) |
I_0_I_6_I |
0 to 63, Blank |
In minutes, Blank = No Bell Output |
|
1.9 |
BzPhFail |
I_NO_I |
Yes/No |
No = No Pulse Buzzer for Comm Failure |
|
1.10 |
BzACFail |
I_NO_I |
Yes/No |
No = No Pulse Buzzer for AC Failure |
|
1.11 |
DTMF |
I_YES_I |
Yes/No |
Yes = TouchTone Dial, No = Pulse Dial |
|
1.12 |
CSPrg |
I_YES_I |
Yes/No |
Yes = Enable Remote Downloading |
|
1.13 |
Cmd43 |
I_YES_I |
Yes/No |
Yes = Enable COMMAND 43 for downloading |
|
1.14 |
Pass |
I_9_I_9_I_9_I_9_I |
0 to 9, B to F, Blank Remote Programming Passcode |
|
1.15 |
AnsArm |
I_0_I_5_I |
0 to 14, Blank |
# of Rings to Answer Downloader if Armed |
|
1.16 |
AnsDis |
I_1_I_2_I |
0 to 14, Blank |
# of Rings to Answer Downloader if Disarmed |
|
1.17 |
AuxRlyTim |
I_ _I_ _I |
2, 5, 10, 15 |
Aux Relay Contact closure time in seconds
|
2. |
|
PriPhone (Primary Phone Variables/Defaults |
|
2.1 |
P |
I_1_I_8_I_0_I_0_I_ _I_ _I_ _I
C = 3 second pause D = 7 sec pause
|
8-digits 0 to 9, C to D, Blank (Phone Prefix) |
|
2.2 |
Ph |
I_?_I_?_I_?_I_?_I_?_I_?_I_?_I |
7-digits 0 to 9, C to D, Blank (Rest of Phone Number) |
|
2.3 |
Modem |
I_YES_I |
Yes/No |
Yes = Modem Format, if No see section 2.4 |
|
2.4 |
CS |
I_6_I |
1 to 6 |
Alternate Format if Modem not selected in 2.3
1 = Silent Knight Low Speed Double Round
2 = Ademco Low Speed Double Round
3 = Silent Knight High Speed Double Round
4 = Ademco High Speed Double Round
5 = Radionics Single Round with Parity Digit
6 = Radionics BFSK Superfast Single Round
Blank = Sescoa, Franklin Hi Speed Double Round
|
|
2.5 |
Ack14 |
I_NO_I |
Yes/No |
Yes = 1400Hz Ack tone, No if Modem Format used |
|
2.6 |
EXT/R |
I_YES_I |
Yes/No |
Expanded Trouble/Restoral by Zone |
|
2.7 |
Ack23 |
I_NO_I |
Yes/No |
Yes = 2300Hz Ack tone, No if Modem Format used
|
3. |
|
AltPhone (Alternate Phone) Variables/Defaults |
|
3.1 |
AP |
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I |
8-digits 0 to 9, C to D, Blank (Do not use) |
|
3.2 |
APh |
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I |
7-digits 0 to 9, Blank (Do not use) |
|
3.3 |
Modem |
I_YES_I |
Yes/No |
Yes = Modem Format, if No see section 3.4 |
|
3.4 |
ACS |
I_7_I |
1 to 6 |
Alternate Format if Modem not selected in 3.3 |
|
3.5 |
AAck14 |
I_NO_I |
Yes/No |
Yes = 1400Hz Ack tone, No if Modem Format used |
|
3.6 |
AExT/R |
I_YES_I |
Yes/No |
Expanded Trouble/Restoral by Zone |
|
3.7
3.8
3.9
|
AlarmRoute
OpClRoute
TblRoute
|
I_0_I
I_0_I
I_0_I
|
0 to 3
0 to 3
0 to 3
|
0 = Primary Phone Only
1 = Primary then Alternate Phone
2 = Alternate then Primary Phone
3 = Non-Designated Zones to Primary Phone
Designated Zones to Alternate Phone
|
|
3.10 |
ResRoute |
I_0_I |
0 to 3 |
|
3.11 |
AAck23 |
I_YES_I |
Yes/No |
Yes = 2300Hz Ack tone, No if Modem Format used |
4. |
|
Devices (Keypads) Variables/Defaults |
|
4.1 |
Device# |
I_?_I |
1 to 4 |
Enter Device Address Number here to select |
|
4.2 |
D1Model |
I_1_I |
1 to 4 |
Enter Model of Device selected in 4.1
1 = D610/D611
2 = D620/D626
3 = D630/D636
4 = D640
|
|
4.3 |
D1Cmd |
I_YES_I |
Yes/No |
Enables COMMAND key on selected Device |
|
4.4 |
D1Acct1 |
I_YES_I |
Yes/No |
Yes = Device uses Account 1, No = Account 2
|
5. |
|
CommandKeys (Function Keys) Variables/Defaults |
|
5.1 |
Comb9 |
I_9_I_ _I_ _I_ _I |
0 to 9, Blank Command Key Security Passcode
(Not used, 1st digit is hardcoded as 9)
|
|
5.2 |
Cmd1 |
I_YES_I |
Yes/No |
Enable Command 1 to Master Arm system |
|
5.3 |
Cmd2 |
I_YES_I |
Yes/No |
Enable Command 2 to Instant Perimeter Arm |
|
5.4 |
Cmd3 |
I_YES_I |
Yes/No |
Enable Command 3 to Delay Perimeter Arm |
|
5.5 |
FA123 |
I_YES_I |
Yes/No |
Commands 1, 2 and 3 will Force Arm system |
|
5.6 |
Cmd0 |
I_YES_I |
Yes/No |
Enable Command 0 for shunting in exit delay |
|
5.7 |
FAMax |
I_1_I |
0 to 9 |
Maximum number of Zones allowed by Force Arming |
|
5.8 |
Cmd8 |
I_YES_I |
Yes/No |
Enable Command 8 for Delay Perimeter arming |
|
5.9 |
Cmd41 |
I_NO_I |
Yes/No |
Enable Command 41 for unexpanded Restorals |
|
5.10 |
Cmd42 |
I_YES_I |
Yes/No |
Enable Command 42 for System Trouble Reports |
|
5.11 |
Cmd44 |
I_YES_I |
Yes/No |
Enable Command 44 for Local system test |
|
5.12 |
Cmd47 |
I_YES_I |
Yes/No |
Enable Command 47 to reset Smoke Detectors |
|
5.13 |
C47Shrt |
I_YES_I |
Yes/No |
Yes = 2-second Reset Time, No = 4 seconds |
|
5.14 |
Cmd5 |
I_YES_I |
Yes/No |
Enable Command 5 for Passcode Change Mode |
|
5.15 |
Cmd6 |
I_YES_I |
Yes/No |
Enable Command 6 for Watch Mode (Door Chimes) |
|
5.16 |
C7RptCd |
I_7_I |
0 to 9, Blank
0 to 9, B to F, Blank
|
(if using 4/2 BFSK) Command 7 Medical Report Code
(if using Modem II)
|
|
5.17 |
C7Bell |
I_NO_I |
Yes/No |
Disable Siren during Command 7 Medical Alarm |
|
5.18 |
C7PisBel |
I_NO_I |
Yes/No |
Pulse Siren during Command 7 Medical Alarm |
|
5.19 |
C7AuxRly |
I_NO_I |
Yes/No |
Activate Aux Relay during Command 7 Medical Alarm |
|
5.20 |
C7DsgZn |
I_NO_I |
Yes/No |
Enable Command 7 as a Desginated Zone |
|
5.21 |
C9RptCd |
I_9_I |
0 to 9, Blank
0 to 9, B to F, Blank
|
(if using 4/2 BFSK) Command 9 Fire Report Code
(if using Modem II)
|
|
5.22 |
C9Bell |
I_YES_I |
Yes/No |
Enable Siren during Command 9 Fire Alarm |
|
5.23 |
C9PisBel |
I_NO_I |
Yes/No |
Pulse Siren during Command 9 Fire Alarm |
|
5.24 |
C9AuxRly |
I_NO_I |
Yes/No |
Activate Aux Relay during Command 9 Fire Alarm |
|
5.25 |
C9DsgZn |
I_NO_I |
Yes/No |
Enable Command 9 as a Desginated Zone |
|
5.26 |
AKey |
I_ _I_ _I |
01 to 09, Blank |
“A” Function Key Operation |
|
5.27 |
BKey |
I_ _I_ _I |
01 to 09, Blank |
“B” Function Key Operation |
|
5.28 |
CKey |
I_ _I_ _I |
01 to 09, Blank |
“C” Function Key Operation |
|
|
01 = CMD 41 Unexpanded Test Report |
06 = CMD 5 Passcode Change Mode |
02 = CMD 42 System Trouble Report |
07 = CMD 6 Perimeter Watch Mode |
03 = CMD 43 Initiate Remote Program |
08 = CMD 7 Keypad Medical Alarm |
04 = CMD 44 Local system Test |
09 = Keypad Police Alarm |
05 = CMD 47 Sensor Reset |
|
6. |
|
Combinations (User Codes) Variables/Defaults |
|
|
_ = Passcode Number |
|
6.1 |
Comb# |
I_?_I |
1 to 7 |
Enter number of Passcode to program |
|
6.2 |
Comb_ |
I_ _I_ _I_ _I_ _I |
0 to 9, Blank Enter 1 to 4 digit Passcode |
|
|
(Passcodes start with user number, Example: Passcode 5 start with 5 + 1 – 4 digits) |
|
6.3 |
C_Ovrd |
I_NO_I |
Yes/No |
Passcode overrides Opening/Closing Restrictions |
|
6.4 |
C_Acct1 |
I_YES_I |
Yes/No |
Passcode Arms/Disarms for Account #1 |
|
6.5 |
C_Acct2 |
I_NO_I |
Yes/No |
Passcode Arms/Disarms for Account #2
|
7. |
|
Account #1 (Partition 1) Variables/Defaults |
|
7.1 |
1Acct |
I_ _I_ _I_ _I_ _I
(1st digit Blank if 3-digit account)
|
0 to 9, B to F, Blank Enter 3 digit Account if BFSK or 4/2 used (Virtual)
Enter 4 digit Account if Modem II used (Radionics)
|
|
7.2 |
1Off |
I_NO_I |
Yes/No |
Yes = Disable all Functions except Remote Program
No = Normal operation
|
|
7.3 |
1Local |
I_NO_I |
Yes/No |
Yes = Disable Central Station Reports (Local System)
No = Enable Central Station Reports
|
|
7.4 |
1DlyIn |
I_30_I |
10 to 120, Blank |
Entry Delay in 10 second increments |
|
7.5 |
1DlyOut |
I_60_I |
10 to 120, Blank |
Exit Delay in 10 second increments |
|
7.6 |
1Prwrn |
I_YES_I |
Yes/No |
Sound Prewarning buzzer during Entry Delay |
|
7.7 |
1Op/Cl |
I_NO_I |
Yes/No |
Enable Opening/Closing Reports for this Account |
|
7.8 |
1ReOp |
I_NO_I |
Yes/No |
Enable Restricted Opening Reports (Disarm on Alarm) |
|
7.9 |
1ReCl |
I_NO_I |
Yes/No |
Enable Restricted Closing Reports
(Send on Force Arm or if Command 0 used to Shunt)
|
|
7.10 |
1CombID |
I_NO_I |
Yes/No |
Identify Opening/Closing Reports by User Passcode |
|
|
|
|
Combination 1 = Zone 1 |
Combination 5 = Zone 5 |
Combination 2 = Zone 2 |
Combination 6 = Zone 6 |
Combination 3 = Zone 3 |
Combination 7 = Zone 7 |
Combination 4 = Zone 4 |
Download or CMD 1 Arming = Zone 9 |
|
|
7.11 |
1CnclRpt |
I_NO_I |
Yes/No |
Enable Cancel Reports for this Account |
|
7.12 |
1Duress |
I_NO_I |
Yes/No |
Enable Duress Reports for this Account
(Duress = 1 digit above User Passcode)
|
|
7.13 |
1DlyRes |
I_NO_I |
Yes/No |
Delay Restoral Reports until Bell Timeout |
|
7.14 |
1Ring1 |
I_YES_I |
Yes/No |
1 Alarm Output per Zone (Swinger Shutdown) |
|
7.15 |
1TsBell |
I_NO_I |
Yes/No |
Automatic Bell Test after Arming |
|
7.16 |
1Show |
I_YES_I |
Yes/No |
Show Zone Status while Disarmed |
|
7.17 |
Acct1Zns |
I_8_I |
1 to 16 |
Total Number of Zones for this Account (Partition) |
|
|
( _ = Zone Number) |
|
7.18 |
1Zone# |
I_?_I |
1 to 16 |
Enter the Zone to Program |
|
7.19 |
Z+Loc |
I_0_I_A_I |
1st Digit = 0 to 4
2nd Digit = A to H
|
1st Digit = Device/Zone Address Location
0 = D6112 Onboard Zones
1 to 4 = D630/D640 Zone Expander Address
2nd Digit = Physical Location of Zone on Device
A = “Zone 1” E = “Zone 5” _A = Disabled
B = “Zone 2” F = “Zone 6”
C = “Zone 3” G = “Zone 7”
D = “Zone 4” H = “Zone 8”
|
|
7.20 |
1Zn1 |
I_ _I_ _I_ _I_ _I_ _I |
0 to 9, B to F Enter 5 digit Zone Type, 00000 = Disabled |
|
Typical Zone Programming |
Delay Zone N/C |
(No Trouble or Restoral Reporting, Swinger Shunt) |
24130 |
Delay Zone N/O |
(No Trouble or Restoral Reporting, Swinger Shunt) |
28130 |
Instant Zone N/C or N/O |
(No Trouble or Restoral Reporting, Swinger Shunt) |
20130 |
Interior Delay Zone N/C |
(No Trouble or Restoral Reporting, Swinger Shunt) |
14130 |
Interior Delay Zone N/O |
(No Trouble or Restoral Reporting, Swinger Shunt) |
18130 |
Interior Instant Zone N/O or N/C |
(No Trouble or Restoral Reporting, Swinger Shunt) |
10130 |
Glassbreak Zone |
(No Trouble or Restoral Reporting) |
20114 |
Window Foil Zone |
(No Trouble or Restoral Reporting) |
20114 |
Fire Zone |
(Trouble Reporting, no Restoral Reporting) |
01414 |
Audible Panic N/C or N/O |
(No Trouble or Restoral Reporting, Invisible Zone) |
00111 |
Silent Panic N/C or N/O |
(No Trouble or Restoral Reporting, Invisible Zone) |
00011 |
Independent Zone Control |
(If D268, D269 and D279 Expander Module is Used) |
01150 |
Digit 1 = Zone Response
0 = 24Hr Zone
1 = Interior Zone
2 = Perimeter Zone
3 = Priority 24Hr Zone
4 = Priority Interior Zone
5 = Priority Perimeter Zone
(Priority Zns can’t be Bypassed or Forced)
Digit 2 = Zone Response to Open or Short
0 = No Trouble, No Delay, Instant on Open or Short
1 = Trouble on Open, Instant on Open or Short
2 = Trouble on Short, Instant on Open or Short
3 = Trouble on Open or Short, Instant on Open or Short
4 = Delay on Open, Instant on Short, No Troubles
5 = Delay on Open, Instant on Short, Trouble on Open
6 = Delay on Open, Trouble on Short, Instant on Short
7 = Delay on Open, Trouble on Open/Short, instant on Short
8 = Delay on Short, Instant on Open, No Troubles
9 = Delay on Short, Instant on Open, Trouble on Open
A = Delay on Short, Instant on Open, Trouble on Short
B = Delay on Short, Instant on Open, Trouble on Open/Short
C = Delay on Open or Short, No Troubles
D = Delay on Open or Short, Trouble on Open
E = Delay on Open or Short, Trouble on Short
F = Delay on Open or Short, Trouble on Open/Short
|
Digit 3 = Zone Local Alarm Response
0 = Silent Alarm, No Alarm Output
1 = Steady Alarm Output for Bells/Sirens
2 = Aux Relay Activation for Bell Timeout
3 = Aux Relay Activation/Steady Alarm Output
4 = Pulsing Alarm Output for Bells/Sirens
5 = Aux Relay Activation
6 = Aux Relay Activation, Pulsing Alarm Output
Digit 4 = Central Station Reporting Options
0 = Non-Reporting, Local Zone Only
1 = Standard Reporting Zone
2 = Designated Zone
3 = Swinger Shunt Zone
4 = Swinger Shunt, Designated Zone
5 = Standard Reporting, includes Restorals
6 = Restoral Reports, Designated Zone
7 = Restoral Reports, Swinger Shunt Zone
8 = Restoral Reports, Designated & Swinger
Digit 5 = Local Annunciation Zones & Options
0 = No Options
1 = Invisible Zone (Doesn’t display on Keypad)
2 = Siren until Zone Restoral
3 = Siren until Zone Restoral, Invisible Zone
4 = Sound Buzzer on Fault
5 = Sound Buzzer on Fault, Invisible Zone
6 = Sound Buzzer on Fault, Rings Sirens
7 = Sound Buzzer on Fault, Ring Bell until
Restoral, Invisible Zone
|
|
8. |
|
Account #2 (Partition 2) Variables/Defaults |
|
8.1 |
1Acct |
I_ _I_ _I_ _I_ _I |
0 to 9, B to F, Blank Enter 3 digit Account if BFSK or 4/2 used (Virtual)
Enter 4 digit Account if Modem II used (Radionics)
|
|
8.2 |
2Off |
I_NO_I |
Yes/No |
Yes = Disable all Functions except Remote Program
No = Normal operation
|
|
8.3 |
2Local |
I_NO_I |
Yes/No |
Yes = Disable Central Station Reports (Local System)
No = Enable Central Station Reports
|
|
8.4 |
2DlyIn |
I_30_I |
10 to 120, Blank |
Entry Delay in 10 second increments |
|
8.5 |
2DlyOut |
I_60_I |
10 to 120, Blank |
Entry Delay in 10 second increments |
|
8.6 |
2Prwrn |
I_YES_I |
Yes/No |
Sound Prewarning buzzer during Entry Delay |
|
8.7 |
2Op/Cl |
I_NO_I |
Yes/No |
Enable Opening/Closing Reports for this Account |
|
8.8 |
2ReOp |
I_NO_I |
Yes/No |
Enable Restricted Opening Reports (Disarm on Alarm) |
|
8.9 |
2ReCl |
I_NO_I |
Yes/No |
Enable Restricted Closing Reports
(Send on Force Arm or if Command 0 used to Shunt)
|
|
8.10 |
2CombID |
I_NO_I |
Yes/No |
Identify Opening/Closing Reports by User Passcode |
|
|
|
|
Combination 1 = Zone 1 |
Combination 5 = Zone 5 |
Combination 2 = Zone 2 |
Combination 6 = Zone 6 |
Combination 3 = Zone 3 |
Combination 7 = Zone 7 |
Combination 4 = Zone 4 |
Download or CMD 1 Arming = Zone 9 |
|
|
8.11 |
2CnclRpt |
I_NO_I |
Yes/No |
Enable Cancel Reports for this Account |
|
8.12 |
2Duress |
I_NO_I |
Yes/No |
Enable Duress Reports for this Account
(Duress = 1 digit above User Passcode)
|
|
8.13 |
2DlyRes |
I_NO_I |
Yes/No |
Delay Restoral Reports until Bell Timeout |
|
8.14 |
2Ring1 |
I_YES_I |
Yes/No |
1 Alarm Output per Zone (Swinger Shutdown) |
|
8.15 |
2TsBell |
I_NO_I |
Yes/No |
Automatic Bell Test after Arming |
|
8.16 |
2Show |
I_YES_I |
Yes/No |
Show Zone Status while Disarmed |
|
8.17 |
Acct2Zns |
I_8_I |
1 to 16 |
Total Number of Zones for this Account (Partition) |
|
|
( _ = Zone Number) |
|
8.18 |
2Zone# |
I_?_I |
1 to 16 |
Enter the Zone to Program |
|
8.19 |
2Z_Loc |
I_0_I_A_I |
1st Digit = 0 to 4
2nd Digit = A to H
|
1st Digit = Device/Zone Address Location
0 = D6112 Onboard Zones
1 to 4 = D630/D640 Zone Expander Address
2nd Digit = Physical Location of Zone on Device
A = “Zone 1” E = “Zone 5” _A = Disabled
B = “Zone 2” F = “Zone 6”
C = “Zone 3” G = “Zone 7”
D = “Zone 4” H = “Zone 8”
|
|
8.20 |
1Zn_ |
I_ _I_ _I_ _I_ _I_ _I |
0 to 9, B to F Enter 5 digit Zone Type, 00000 = Disabled
(See Zone 1 Programming)
|
9. |
|
Test Timer Variables/Defaults |
|
9.1 |
TsPPh |
I_NO_I |
Yes/No |
Transmit Auto-Test Report to Primary Phone |
|
9.2 |
TsAPh |
I_NO_I |
Yes/No |
Transmit Auto-Test Report to Alternate Phone |
|
9.3 |
Days |
I_YES_I |
Yes/No |
Yes = Interval in Days, No = Interval in Hours |
|
9.4 |
Intvl |
I_0_I |
0 to 63 |
Automatic Test Time Interval Days or Hours |
|
9.5 |
DysRpt |
I_0_I |
0 to 63 |
Number of Days until first Automatic Test Report |
|
9.6 |
HrsRpt |
I_0_I |
0 to 63 |
Number of Hours until first Automatic Test Report |
|
9.7 |
TsCode |
I_ _I |
0 to 9, Blank
0 to 9, B to F, Blank
|
(BFSK or Pulse Format) Automatic Test Code
(Modem II Format)
|
|
9.8 |
TsE |
I_NO_I |
Yes/No |
Transmit Restoral Code E at Auto Test Report Time |
|
9.9 |
TsDef |
I_NO_I |
Yes/No |
Defer Test Report when System Report Generated |