SIA Format

AN An analog fire sensor has been restored Zone
AR AC restoral AC power has been restored Zone
AS Analog fire sensor needs to be cleaned or calibrated Zone
AT AC trouble AC power has been failed Unused Unused
BA Burglary alarm Burglary Zone has been violated while armed Zone
BB Burglary bypass Burglary Zone has been bypassed Zone
BC Burglary cancel Alarm has been cancelled User
BD Zone Swinger Trouble Zone
BE Zone Swinger Trouble Restore Zone
BH Burglary A. rest. Alarm condition eliminated Zone
BJ Burglary T. rest. Trouble condition eliminated Zone
BM Burglary alarm w/cross point – Alarm verified Zone
BR Burglary restoral Alarm/trouble condition eliminated Zone
BS Burglary supervisory. Unsafe intrusion detection condition Zone
BT Burglary trouble Burglary Zone activated during testing Zone
BU Burglary unbypass Zone bypass has been removed Zone
BV Burglary Verified More than 3 burglary Zones have been triggered Zone
BX Burglary test Burglary Zone activated during testing Zone
BZ Missing Supervision Zone
CA Automatic closing System armed automatically Area
CD The system has not been armed for a programmed amount of time Area
CE Closing extend Extend closing time User
CF Forced closing System armed, some Zones not ready User
CG Close Area System has been partially armed User
CI Fail to close An Area has not been armed at end of closing window User
CJ Late close An Area was armed after the closing window User
CK Early close An Area was armed before the closing window User
CL Closing report System armed normal User
CM A point has gone missing within 2 mintes of closing Zone
CP Automatic closing System armed automatically User
CR Recent Closing, alarm occurred five minutes after system closed User
CS Closing switch Account has been armed by Keyswitch Zone
CT Late to open System was not disarmed on time Area
CW Was force armed Header for force armed session May follow Area
CZ Point closing A Point, as opposed to Area or account, has closed Zone
DA An access ID has been added to the controller User
DB An access ID has been deleted from the controller User
DC Access closed Access to all Users prohibited Door
DD Access denied Access denied, unknown code Door
DE An access point was opened via a Request to Enter Device Door
DF Door forced Door opened without access request Door
DG Access granted Door access granted Door
DH An access point in a Door Left Open state has restored Door
DJ An access point has been forced open in an unarmed area Door
DK Access lockout Access denied, known code Door
DL An open access point when open time expired in an open area Door
DM An open access point when open time expired in an unarmed area Door
DN An access point was open when the door cycle time expired Door
DO Access open Access to authorised Users allowed Door
DP An access request was denied: The request is outside the approved time Door
DQ An access request was denied: The user is not authorized in the armed area Door
DR Door restoral access alarm/trouble condition eliminated Door
DS Door station Identifies Door for next report Door
DT Access trouble Access system trouble Unused
DU Dealer ID Zone description gives dealer ID # Dealer ID
DV An access request was denied: The user is not authorized in the area Door
DW An access request was denied: The doors associated Interlock point were open Door
DX An access point was opened via a Request to Exit Device Door
DY The door’s lock has been engaged Door
DZ An access request was denied: Access Closed State Door
EA Exit Alarm Zone
EE Exit error, Zone remained violated at end of exit delay period User
ER Expansion rest. Expansion device trouble eliminated Expander #
ET Expansion trouble Expansion device trouble Expander #
EX A specific reportable condition is detected on an external device Device
EZ A point remained missing at the end of the exit delay period Point
FA Fire alarm Fire condition detected Zone
FB Fire bypass Zone has been bypassed Zone
FC A fire alarm has been cancelled by an authorized person Zone
FH Fire Alarm restore Alarm condition eliminated Zone
FI Fire test begin The transmitter Area’s fire test has begun Area
FJ Fire Trouble restore Trouble condition eliminated Zone
FK Fire test end The transmitter Area’s fire test has ended Area
FM Fire alarm with cross point also in alarm verifying the fire alarm Point
FR Fire restoral Alarm/trouble condition has been eliminated Zone
FS Fire supervisory Unsafe fire detection system condition Zone
FT Fire trouble Zone disabled by fault Zone
FU Fire unbypass Bypass has been removed Zone
FX Fire test Fire Zone activated during test Zone
FY Missing fire Trouble A fire Point is now logically missing Zone
FZ A fire supervisory point has gone missing Zone
GA Gas alarm Gas alarm condition detected Zone
GB Gas bypass Zone has been bypassed Zone
GH Gas A. restore Alarm condition eliminated Zone
GJ Gas T. restore Trouble condition eliminated Zone
GR Gas restoral Alarm \ trouble condition has been eliminated Zone
GS Gas supervisory Unsafe gas detection system condition Zone
GT Gas trouble Zone disabled by fault Zone
GU Gas unbypass Bypass has been removed Zone
GX Gas test gas Zone activated during test Zone
HA Hold-up alarm Silent alarm, User under duress Zone
HB Hold-up bypass Zone has been bypassed Zone
HH Hold-up A. rest. Alarm condition eliminated Zone
HJ Hold-up T. rest. Trouble condition eliminated Zone
HR Hold-up restoral Alarm \ trouble condition eliminated Zone
HS Hold-up supervisory. Unsafe holdup system condition Zone
HT Hold-up trouble Zone disabled by default Zone
HU Hold-up unbypass Bypass has been removed Zone
IA A specific reportable condition is detected on a device Point
IR The equipment condition has been restored to normal Point
JA User code tamper Too many unsuccessful attempts User ID, Area
JD Date changed The date was changed in the transmitter/receiver User
JH Holiday changed, transmitter’s holiday schedule has changed User
JL Log threshold, transmitter’s log memory has reached Threshold Unused
JO Log overflow The transmitter’s log memory has overflowed Unused
JP A designated user passcode has been used to disarm the panel User
JR Schedule execute An automatic scheduled event was executed Area
JS Schedule change An automatic schedule was changed User
JT Time changed The time was changed in the TX\RX User
JV User code change A User’s code has been changed User
JX User code delete A User’s code has been removed User
JY A users code has been added User
JZ A users authority level has been set User
KA Heat alarm High temperature detected on premise Zone
KB Heat bypass Zone has been bypassed Zone
KH Heat Alarm restore Alarm condition eliminated Zone
KJ Heat Trouble restore Trouble condition eliminated Zone
KR Heat restoral Alarm/Trouble condition has been eliminated Zone
KS Heat supervisory Unsafe heat detection system condition Zone
KT Heat trouble Zone disable by fault Zone
KU Heat unbypass Bypass has been removed Zone
LB Local program Begin local programming begin Unused
LD Local program Denied access code incorrect Unused
LE Listen-in ended The listen-in session has been terminated Unused
LF Listen-in begin Unused
LR Phone line rest. Phone line restored to service Line
LS Local program Local programming successful Unused
LT Phone line Trouble Phone line report Line
LU Local program fail Local programming unsuccessful Unused
LX Local program ended Unused
MA Medical alarm Emergency assistance request Zone
MB Medical bypass Zone has been bypassed Zone
MH Medical Alarm restore Alarm condition eliminated Zone
MJ Medical T. rest. Trouble condition eliminated Zone
MR Medical restoral Alarm/trouble condition has been eliminated Zone
MS Medical supervisory Unsafe system condition exists Zone
MT Medical trouble Zone disabled by fault Zone
MU Medical unbypass Bypass has been removed Zone
MX Medical Test Zone
NA No activity There has been no activity for a programmed amount of time Unused
NC A communication network has a specific reportbale condition Network
NF Forced perimeter arm Some Zones/Points not ready Area
NL Perimeter armed An Area has been perimeter armed Area
NR A communications network has returned to normal operation Network
NS A zone has detected activity after an alert Zone
NT A communications network has failed Network
OA Automatic opening System has disarm automatically Area
OC Cancel report Untyped Zone cancel User
OG Open Area System has been partially disarmed Area
OH An area in alarm was disarmed before the opening window User
OI Fail to open An Area has not been armed at the end of opening window Area
OJ Late open An Area was disarmed after the opening window User
OK Early open An Area was disarmed before the opening window User
OL An area in alarm was disarmed after the opening window User
OP Opening report Account was disarmed User
OR Disarm from alarm Account in alarm was reset/disarmed User
OS Opening Keyswitch account has been disarmed by Keyswitch Zone
OT Late to close System was not armed on time User
OZ Point opening A Point, rather than a full Area or account, disarmed Zone
PA Panic alarm Emergency assistance request, manually activated Zone
PB Panic bypass Panic Zone has been bypassed Zone
PH Panic Alarm restore Alarm condition eliminated Zone
PJ Panic Trouble restore Trouble condition eliminated Zone
PR Panic restoral Alarm/trouble condition has been eliminated Zone
PS Panic Supervisory Unsafe system condition exists Zone
PT Panic trouble Zone disabled by fault Zone
PU Panic unbypass Panic Zone bypass has been removed Zone
QA Emergency alarm Emergency assistance request Zone
QB Emergency bypass Zone has been bypassed Zone
QH Emergency. A. rest. Alarm condition has been eliminated Zone
QJ Emergency. T. rest. Trouble condition has been eliminated Zone
QR Emergency. Restoral Alarm/trouble condition has been eliminated Zone
QS Emergency. Supervisory Unsafe system condition exists Zone
QT Emergency Trouble Zone disabled by fault Zone
QU Emergency. Unbypass Bypass has been removed Zone
RA Remote Programmer, Transmitter failed to communicate with programmer Unused
RB Remote Program begin Remote programming session initiated Unused
RC Relay close relay specified in address field (optional) has energised Relay
RD Remote Program Denied Access passcode incorrect Unused
RN A transmitter was reset via a remote programmer Unused
RO Relay open or has de-energised Relay
RP Automatic test Automatic communication test report Unused
RR Power up System lost power, is now restored Unused
RS Remote Program success Remote programming successful Unused
RT Data lost Dialer data lost, transmission error Line
RU Remote Program fail Remote programming unsuccessful Unused
RX Manual test Manual communication test report User
RY Manual Test with trouble condition User
SA Sprinkler alarm Sprinkler flow condition exist Zone
SB Sprinkler. Bypass Sprinkler Zone has been bypassed Zone
SH Sprinkler. Alarm restore Alarm condition eliminated Zone
SJ Sprinkler. Trouble restore trouble condition eliminated Zone
SR Sprinkler. Restore Alarm/Trouble condition has been eliminated Zone
SS Sprinkler. supervisory. Unsafe sprinkler system condition Zone
ST Sprinkler. Trouble Zone disabled by fault Zone
SU Sprinkler. unbypass Sprinkler Zone bypass has been removed Zone
TA Tamper alarm Alarm equipment enclosure opened Zone
TB Tamper bypass Tamper detection has been bypassed Zone
TC All points tested Unused
TE Test end Communicator restored to operation Unused
TP This point was tested during a walk test Point
TR Tamper restoral Alarm equipment enclosure has been closed Zone
TS Test start Communicator taken out of operation Unused
TT Equipment enclosure opened in disarmed state Zone
TU Tamper unbypass Tamper detection bypass has been removed Zone
TX Test Report, unspecified (manual/automatic) communicator test Zone
UA Untyped Zone Alarm Alarm condition from Zone of unknown type Zone
UB Untyped Zone Bypass Zone of unknown type has been bypassed Zone
UH Untyped Alarm restoral Alarm condition eliminated Zone
UJ Untyped Trouble restoral Trouble condition eliminated Zone
UR Untyped Zone restoral Alarm/Troubl Zone
US Untyped Zone sup. Unsafe condition from Zone OK unknown type Zone
UT Untyped Zone Trouble Trouble condition from Zone unknown type Zone
UU Untyped Zone unbypass Bypass on Zone unknown type removed Zone
UX Undefined An undefined alarm condition has occurred Unused
UY Untyped missing Trouble A Point now logically missing Zone
UZ Untyped missing Alarm A Point now logically missing Zone
VI Printer paper in Transmitter or receiver paper in, printer X printer
VO Printer paper out Transmitter or receiver paper out, printer X printer
VR Printer restore Transmitter or receiver trouble restored, printer X printer
VT Printer trouble Transmitter or receiver trouble, printer X printer
VX Printer test Transmitter or receiver test, printer X printer
VY Printer on line The receiver’s printer is now on line Unused
VZ Printer off line The receiver’s printer is now off line Unused
WA Water alarm Water detected at protected premise Zone
WB Water bypass Water detection has been bypassed Zone
WH Water alarm restoral Alarm condition eliminated Zone
WJ Water trouble restoral Trouble condition eliminated Zone
WR Water restoral Alarm/Trouble condition has been eliminated Zone
WS Water supervisory Unsafe water detection system condition Zone
WT Water trouble Zone disable by fault Zone
WU Water unbypass Water detection bypass has been removed Zone
XA CS Receiver has received an event from a non-existant account Unused
XE Extra Point panel has sensed extra Point not specified for this site Point
XF Extra RF Point not specified for this site Point
XH A radio device is no longer detecting RF Interface Receiver Number
XI Sensor reset A User has reset a sensor Zone
XJ A tamper condition at a premises RF Receiver has been restored Receiver Number
XL The RF signal strength of a reported event is below minimum level Receiver Number
XM Missing alarm verified by Cross Point in alarm (or missing) Zone
XQ A radio device is detecting RF Interface Receiver Number
XR TX battery restoral Low battery has been corrected Zone
XS A tamper condition at a premises receiver is detected Receiver Number
XT TX battery trouble Low battery in wireless transmitter Zone
XW Forced Point A Point was forced out of the system at arm time Zone
XX A specific test from a panel was not received Unused
YA A trouble condition has been detected on a local Bell, Siren, or Annunciator Unused
YB Busy seconds Percent of time receiver’s line card is on-line Line
YC Communication fail Receiver and transmitter Unused
YD RX line card trouble A line card identified by passed address is in trouble Line
YE RX line card restoral A line card identified by passed address is restored Line
YF Parameter checksum fail System data corrupted Unused
YG Parameter changed A transmitter’s parameters have changed Unused
YH A trouble condition has been restored on a local Bell, Siren, or Annunciator Unused
YK Communication Restoral, transmitter has resumed communication Unused
YM System battery missing, transmitter/receiver battery is missing Unused
YN Invalid report The transmitter has sent a packet with invalid data Unused
YO Unknown message was received from automation or printer Unused
YP Power supply trouble Unused
YQ Power supply restored Unused
YR System battery restoral Low battery has been corrected Unused
YS Communication trouble Receiver and transmitter Unused
YT System battery trouble Low battery in control/communicator Unused
YW Watchdog reset The transmitter created an internal reset Unused
YX Service required a transmitter/receiver needs service Unused
YY Status report, This is a header for account status report transmission Unused
YZ Service completed required transmitter/Receiver service completed MFR Defined
ZA Freeze alarm Low temperature detected at premise Zone
ZB Freeze bypass Low temperature detection has been bypassed Zone
ZH Freeze A. restore Alarm condition eliminated Zone
ZJ Freeze T. restore Trouble condition eliminated Zone
ZR Freeze restoral Alarm/Trouble condition has been eliminated Zone
ZS Freeze supervisory Unsafe freeze detection system condition Zone
ZT Freeze trouble Zone disabled by fault Zone
ZU Freeze unbypass Low temperature detection bypass removed Zone