AN |
An analog fire sensor has been restored Zone |
AR |
AC restoral AC power has been restored Zone |
AS |
Analog fire sensor needs to be cleaned or calibrated Zone |
AT |
AC trouble AC power has been failed Unused Unused |
BA |
Burglary alarm Burglary Zone has been violated while armed Zone |
BB |
Burglary bypass Burglary Zone has been bypassed Zone |
BC |
Burglary cancel Alarm has been cancelled User |
BD |
Zone Swinger Trouble Zone |
BE |
Zone Swinger Trouble Restore Zone |
BH |
Burglary A. rest. Alarm condition eliminated Zone |
BJ |
Burglary T. rest. Trouble condition eliminated Zone |
BM |
Burglary alarm w/cross point – Alarm verified Zone |
BR |
Burglary restoral Alarm/trouble condition eliminated Zone |
BS |
Burglary supervisory. Unsafe intrusion detection condition Zone |
BT |
Burglary trouble Burglary Zone activated during testing Zone |
BU |
Burglary unbypass Zone bypass has been removed Zone |
BV |
Burglary Verified More than 3 burglary Zones have been triggered Zone |
BX |
Burglary test Burglary Zone activated during testing Zone |
BZ |
Missing Supervision Zone |
CA |
Automatic closing System armed automatically Area |
CD |
The system has not been armed for a programmed amount of time Area |
CE |
Closing extend Extend closing time User |
CF |
Forced closing System armed, some Zones not ready User |
CG |
Close Area System has been partially armed User |
CI |
Fail to close An Area has not been armed at end of closing window User |
CJ |
Late close An Area was armed after the closing window User |
CK |
Early close An Area was armed before the closing window User |
CL |
Closing report System armed normal User |
CM |
A point has gone missing within 2 mintes of closing Zone |
CP |
Automatic closing System armed automatically User |
CR |
Recent Closing, alarm occurred five minutes after system closed User |
CS |
Closing switch Account has been armed by Keyswitch Zone |
CT |
Late to open System was not disarmed on time Area |
CW |
Was force armed Header for force armed session May follow Area |
CZ |
Point closing A Point, as opposed to Area or account, has closed Zone |
DA |
An access ID has been added to the controller User |
DB |
An access ID has been deleted from the controller User |
DC |
Access closed Access to all Users prohibited Door |
DD |
Access denied Access denied, unknown code Door |
DE |
An access point was opened via a Request to Enter Device Door |
DF |
Door forced Door opened without access request Door |
DG |
Access granted Door access granted Door |
DH |
An access point in a Door Left Open state has restored Door |
DJ |
An access point has been forced open in an unarmed area Door |
DK |
Access lockout Access denied, known code Door |
DL |
An open access point when open time expired in an open area Door |
DM |
An open access point when open time expired in an unarmed area Door |
DN |
An access point was open when the door cycle time expired Door |
DO |
Access open Access to authorised Users allowed Door |
DP |
An access request was denied: The request is outside the approved time Door |
DQ |
An access request was denied: The user is not authorized in the armed area Door |
DR |
Door restoral access alarm/trouble condition eliminated Door |
DS |
Door station Identifies Door for next report Door |
DT |
Access trouble Access system trouble Unused |
DU |
Dealer ID Zone description gives dealer ID # Dealer ID |
DV |
An access request was denied: The user is not authorized in the area Door |
DW |
An access request was denied: The doors associated Interlock point were open Door |
DX |
An access point was opened via a Request to Exit Device Door |
DY |
The door’s lock has been engaged Door |
DZ |
An access request was denied: Access Closed State Door |
EA |
Exit Alarm Zone |
EE |
Exit error, Zone remained violated at end of exit delay period User |
ER |
Expansion rest. Expansion device trouble eliminated Expander # |
ET |
Expansion trouble Expansion device trouble Expander # |
EX |
A specific reportable condition is detected on an external device Device |
EZ |
A point remained missing at the end of the exit delay period Point |
FA |
Fire alarm Fire condition detected Zone |
FB |
Fire bypass Zone has been bypassed Zone |
FC |
A fire alarm has been cancelled by an authorized person Zone |
FH |
Fire Alarm restore Alarm condition eliminated Zone |
FI |
Fire test begin The transmitter Area’s fire test has begun Area |
FJ |
Fire Trouble restore Trouble condition eliminated Zone |
FK |
Fire test end The transmitter Area’s fire test has ended Area |
FM |
Fire alarm with cross point also in alarm verifying the fire alarm Point |
FR |
Fire restoral Alarm/trouble condition has been eliminated Zone |
FS |
Fire supervisory Unsafe fire detection system condition Zone |
FT |
Fire trouble Zone disabled by fault Zone |
FU |
Fire unbypass Bypass has been removed Zone |
FX |
Fire test Fire Zone activated during test Zone |
FY |
Missing fire Trouble A fire Point is now logically missing Zone |
FZ |
A fire supervisory point has gone missing Zone |
GA |
Gas alarm Gas alarm condition detected Zone |
GB |
Gas bypass Zone has been bypassed Zone |
GH |
Gas A. restore Alarm condition eliminated Zone |
GJ |
Gas T. restore Trouble condition eliminated Zone |
GR |
Gas restoral Alarm \ trouble condition has been eliminated Zone |
GS |
Gas supervisory Unsafe gas detection system condition Zone |
GT |
Gas trouble Zone disabled by fault Zone |
GU |
Gas unbypass Bypass has been removed Zone |
GX |
Gas test gas Zone activated during test Zone |
HA |
Hold-up alarm Silent alarm, User under duress Zone |
HB |
Hold-up bypass Zone has been bypassed Zone |
HH |
Hold-up A. rest. Alarm condition eliminated Zone |
HJ |
Hold-up T. rest. Trouble condition eliminated Zone |
HR |
Hold-up restoral Alarm \ trouble condition eliminated Zone |
HS |
Hold-up supervisory. Unsafe holdup system condition Zone |
HT |
Hold-up trouble Zone disabled by default Zone |
HU |
Hold-up unbypass Bypass has been removed Zone |
IA |
A specific reportable condition is detected on a device Point |
IR |
The equipment condition has been restored to normal Point |
JA |
User code tamper Too many unsuccessful attempts User ID, Area |
JD |
Date changed The date was changed in the transmitter/receiver User |
JH |
Holiday changed, transmitter’s holiday schedule has changed User |
JL |
Log threshold, transmitter’s log memory has reached Threshold Unused |
JO |
Log overflow The transmitter’s log memory has overflowed Unused |
JP |
A designated user passcode has been used to disarm the panel User |
JR |
Schedule execute An automatic scheduled event was executed Area |
JS |
Schedule change An automatic schedule was changed User |
JT |
Time changed The time was changed in the TX\RX User |
JV |
User code change A User’s code has been changed User |
JX |
User code delete A User’s code has been removed User |
JY |
A users code has been added User |
JZ |
A users authority level has been set User |
KA |
Heat alarm High temperature detected on premise Zone |
KB |
Heat bypass Zone has been bypassed Zone |
KH |
Heat Alarm restore Alarm condition eliminated Zone |
KJ |
Heat Trouble restore Trouble condition eliminated Zone |
KR |
Heat restoral Alarm/Trouble condition has been eliminated Zone |
KS |
Heat supervisory Unsafe heat detection system condition Zone |
KT |
Heat trouble Zone disable by fault Zone |
KU |
Heat unbypass Bypass has been removed Zone |
LB |
Local program Begin local programming begin Unused |
LD |
Local program Denied access code incorrect Unused |
LE |
Listen-in ended The listen-in session has been terminated Unused |
LF |
Listen-in begin Unused |
LR |
Phone line rest. Phone line restored to service Line |
LS |
Local program Local programming successful Unused |
LT |
Phone line Trouble Phone line report Line |
LU |
Local program fail Local programming unsuccessful Unused |
LX |
Local program ended Unused |
MA |
Medical alarm Emergency assistance request Zone |
MB |
Medical bypass Zone has been bypassed Zone |
MH |
Medical Alarm restore Alarm condition eliminated Zone |
MJ |
Medical T. rest. Trouble condition eliminated Zone |
MR |
Medical restoral Alarm/trouble condition has been eliminated Zone |
MS |
Medical supervisory Unsafe system condition exists Zone |
MT |
Medical trouble Zone disabled by fault Zone |
MU |
Medical unbypass Bypass has been removed Zone |
MX |
Medical Test Zone |
NA |
No activity There has been no activity for a programmed amount of time Unused |
NC |
A communication network has a specific reportbale condition Network |
NF |
Forced perimeter arm Some Zones/Points not ready Area |
NL |
Perimeter armed An Area has been perimeter armed Area |
NR |
A communications network has returned to normal operation Network |
NS |
A zone has detected activity after an alert Zone |
NT |
A communications network has failed Network |
OA |
Automatic opening System has disarm automatically Area |
OC |
Cancel report Untyped Zone cancel User |
OG |
Open Area System has been partially disarmed Area |
OH |
An area in alarm was disarmed before the opening window User |
OI |
Fail to open An Area has not been armed at the end of opening window Area |
OJ |
Late open An Area was disarmed after the opening window User |
OK |
Early open An Area was disarmed before the opening window User |
OL |
An area in alarm was disarmed after the opening window User |
OP |
Opening report Account was disarmed User |
OR |
Disarm from alarm Account in alarm was reset/disarmed User |
OS |
Opening Keyswitch account has been disarmed by Keyswitch Zone |
OT |
Late to close System was not armed on time User |
OZ |
Point opening A Point, rather than a full Area or account, disarmed Zone |
PA |
Panic alarm Emergency assistance request, manually activated Zone |
PB |
Panic bypass Panic Zone has been bypassed Zone |
PH |
Panic Alarm restore Alarm condition eliminated Zone |
PJ |
Panic Trouble restore Trouble condition eliminated Zone |
PR |
Panic restoral Alarm/trouble condition has been eliminated Zone |
PS |
Panic Supervisory Unsafe system condition exists Zone |
PT |
Panic trouble Zone disabled by fault Zone |
PU |
Panic unbypass Panic Zone bypass has been removed Zone |
QA |
Emergency alarm Emergency assistance request Zone |
QB |
Emergency bypass Zone has been bypassed Zone |
QH |
Emergency. A. rest. Alarm condition has been eliminated Zone |
QJ |
Emergency. T. rest. Trouble condition has been eliminated Zone |
QR |
Emergency. Restoral Alarm/trouble condition has been eliminated Zone |
QS |
Emergency. Supervisory Unsafe system condition exists Zone |
QT |
Emergency Trouble Zone disabled by fault Zone |
QU |
Emergency. Unbypass Bypass has been removed Zone |
RA |
Remote Programmer, Transmitter failed to communicate with programmer Unused |
RB |
Remote Program begin Remote programming session initiated Unused |
RC |
Relay close relay specified in address field (optional) has energised Relay |
RD |
Remote Program Denied Access passcode incorrect Unused |
RN |
A transmitter was reset via a remote programmer Unused |
RO |
Relay open or has de-energised Relay |
RP |
Automatic test Automatic communication test report Unused |
RR |
Power up System lost power, is now restored Unused |
RS |
Remote Program success Remote programming successful Unused |
RT |
Data lost Dialer data lost, transmission error Line |
RU |
Remote Program fail Remote programming unsuccessful Unused |
RX |
Manual test Manual communication test report User |
RY |
Manual Test with trouble condition User |
SA |
Sprinkler alarm Sprinkler flow condition exist Zone |
SB |
Sprinkler. Bypass Sprinkler Zone has been bypassed Zone |
SH |
Sprinkler. Alarm restore Alarm condition eliminated Zone |
SJ |
Sprinkler. Trouble restore trouble condition eliminated Zone |
SR |
Sprinkler. Restore Alarm/Trouble condition has been eliminated Zone |
SS |
Sprinkler. supervisory. Unsafe sprinkler system condition Zone |
ST |
Sprinkler. Trouble Zone disabled by fault Zone |
SU |
Sprinkler. unbypass Sprinkler Zone bypass has been removed Zone |
TA |
Tamper alarm Alarm equipment enclosure opened Zone |
TB |
Tamper bypass Tamper detection has been bypassed Zone |
TC |
All points tested Unused |
TE |
Test end Communicator restored to operation Unused |
TP |
This point was tested during a walk test Point |
TR |
Tamper restoral Alarm equipment enclosure has been closed Zone |
TS |
Test start Communicator taken out of operation Unused |
TT |
Equipment enclosure opened in disarmed state Zone |
TU |
Tamper unbypass Tamper detection bypass has been removed Zone |
TX |
Test Report, unspecified (manual/automatic) communicator test Zone |
UA |
Untyped Zone Alarm Alarm condition from Zone of unknown type Zone |
UB |
Untyped Zone Bypass Zone of unknown type has been bypassed Zone |
UH |
Untyped Alarm restoral Alarm condition eliminated Zone |
UJ |
Untyped Trouble restoral Trouble condition eliminated Zone |
UR |
Untyped Zone restoral Alarm/Troubl Zone |
US |
Untyped Zone sup. Unsafe condition from Zone OK unknown type Zone |
UT |
Untyped Zone Trouble Trouble condition from Zone unknown type Zone |
UU |
Untyped Zone unbypass Bypass on Zone unknown type removed Zone |
UX |
Undefined An undefined alarm condition has occurred Unused |
UY |
Untyped missing Trouble A Point now logically missing Zone |
UZ |
Untyped missing Alarm A Point now logically missing Zone |
VI |
Printer paper in Transmitter or receiver paper in, printer X printer |
VO |
Printer paper out Transmitter or receiver paper out, printer X printer |
VR |
Printer restore Transmitter or receiver trouble restored, printer X printer |
VT |
Printer trouble Transmitter or receiver trouble, printer X printer |
VX |
Printer test Transmitter or receiver test, printer X printer |
VY |
Printer on line The receiver’s printer is now on line Unused |
VZ |
Printer off line The receiver’s printer is now off line Unused |
WA |
Water alarm Water detected at protected premise Zone |
WB |
Water bypass Water detection has been bypassed Zone |
WH |
Water alarm restoral Alarm condition eliminated Zone |
WJ |
Water trouble restoral Trouble condition eliminated Zone |
WR |
Water restoral Alarm/Trouble condition has been eliminated Zone |
WS |
Water supervisory Unsafe water detection system condition Zone |
WT |
Water trouble Zone disable by fault Zone |
WU |
Water unbypass Water detection bypass has been removed Zone |
XA |
CS Receiver has received an event from a non-existant account Unused |
XE |
Extra Point panel has sensed extra Point not specified for this site Point |
XF |
Extra RF Point not specified for this site Point |
XH |
A radio device is no longer detecting RF Interface Receiver Number |
XI |
Sensor reset A User has reset a sensor Zone |
XJ |
A tamper condition at a premises RF Receiver has been restored Receiver Number |
XL |
The RF signal strength of a reported event is below minimum level Receiver Number |
XM |
Missing alarm verified by Cross Point in alarm (or missing) Zone |
XQ |
A radio device is detecting RF Interface Receiver Number |
XR |
TX battery restoral Low battery has been corrected Zone |
XS |
A tamper condition at a premises receiver is detected Receiver Number |
XT |
TX battery trouble Low battery in wireless transmitter Zone |
XW |
Forced Point A Point was forced out of the system at arm time Zone |
XX |
A specific test from a panel was not received Unused |
YA |
A trouble condition has been detected on a local Bell, Siren, or Annunciator Unused |
YB |
Busy seconds Percent of time receiver’s line card is on-line Line |
YC |
Communication fail Receiver and transmitter Unused |
YD |
RX line card trouble A line card identified by passed address is in trouble Line |
YE |
RX line card restoral A line card identified by passed address is restored Line |
YF |
Parameter checksum fail System data corrupted Unused |
YG |
Parameter changed A transmitter’s parameters have changed Unused |
YH |
A trouble condition has been restored on a local Bell, Siren, or Annunciator Unused |
YK |
Communication Restoral, transmitter has resumed communication Unused |
YM |
System battery missing, transmitter/receiver battery is missing Unused |
YN |
Invalid report The transmitter has sent a packet with invalid data Unused |
YO |
Unknown message was received from automation or printer Unused |
YP |
Power supply trouble Unused |
YQ |
Power supply restored Unused |
YR |
System battery restoral Low battery has been corrected Unused |
YS |
Communication trouble Receiver and transmitter Unused |
YT |
System battery trouble Low battery in control/communicator Unused |
YW |
Watchdog reset The transmitter created an internal reset Unused |
YX |
Service required a transmitter/receiver needs service Unused |
YY |
Status report, This is a header for account status report transmission Unused |
YZ |
Service completed required transmitter/Receiver service completed MFR Defined |
ZA |
Freeze alarm Low temperature detected at premise Zone |
ZB |
Freeze bypass Low temperature detection has been bypassed Zone |
ZH |
Freeze A. restore Alarm condition eliminated Zone |
ZJ |
Freeze T. restore Trouble condition eliminated Zone |
ZR |
Freeze restoral Alarm/Trouble condition has been eliminated Zone |
ZS |
Freeze supervisory Unsafe freeze detection system condition Zone |
ZT |
Freeze trouble Zone disabled by fault Zone |
ZU |
Freeze unbypass Low temperature detection bypass removed Zone
|