Enter Program |
Run jumper from terminals 3 and 6, hold 8 key 3 seconds |
Exit Program |
Remove Jumper, press * and # |
Move to Location |
Press [B] + 2 digit location
1 = scroll through digits
2 = Clears display
3 = Advances to next location
|
|
Zone 1
Zones 2 & 3
Zones 4 and 6
Zone 5
|
must be E/E
must be Follower
must be Instant
can be Instant Zone, Panic and/or Holdup
|
|
|
Report Options |
|
B11 = User Code 1 (Master) |
? ? ? ? |
(4-digits, can’t use 0) |
B12 = User Code 2 |
? ? ? ? |
B13 = User Code 3 |
? ? ? ? |
B14 = User Code 4 |
? ? ? ? |
B15 = Entry Delay |
? |
(x10 seconds) |
B16 = Exit Delay |
? |
(x10 seconds) |
B17 = Enable 1 digit Arming |
? |
Note: Above sections can be accessed in User Programming. Press 8 for 3 secs then Master Code |
B29 = Report on Alarm
Report Enable Zns 1 to 4
Report Enable Zns 5, 6 & Panic
|
Entry is F & 3 F 3
|
B45 = Misc Report Enable
Fire/Duress, Fire Trouble
Low Battery Trouble
|
Entry is 3 & _ 3 _ |
B39 = Restores Enabled
* = Blank this section
|
Entry is _ _ |
B49 = Misc Restores
* = Blank this section
|
Entry is _ _ |
|
|
Report Codes |
|
B21 – B26, B41 – B42 |
B31 – B36, B46 – B47 |
B21 – Zone 1
B22 – Zone 2
B23 – Zone 3
B24 – Zone 4
B25 – Zone 5*
B26 – Zone 6
B41 – No AC Trouble
B42 – Low Battery
|
3 1
3 2
3 3
3 4
0 2
3 6
_ _
7 8
|
B31 – Zone 1 Restore
B32 – Zone 2 Restore
B33 – Zone 3 Restore
B34 – Zone 4 Restore
B35 – Zone 5 Restore
B36 – Zone 6 Restore
B46 – AC Restore
B47 – Low Batt Restore
|
_ _
_ _
_ _
_ _
_ _
_ _
_ _
_ _
|
*Zone 5 is Police Panic * & # |
_ _ = All Blank |
|
|
Opening/Closings/Cancel |
|
B43 – Closing Report |
_ |
B44 – Force Arm Report |
_ |
B48 – Opening Report |
D |
|
|
Account Numbers |
|
B51 = Last 4 of Account |
B52 = Last 4 of Account |
Note: Last 4 of Account must be entered in both sections |
|
|
Phone Numbers |
|
B52 = Report Format Phone 1 |
_ 0 (Ademco Slow, 4/2+2300) |
B53 = Receiver 1 Phone |
_ _ E 1 8 0 0 x x x x x x x (first 2 entries blank) |
B55 = Receiver Format Phone 2 |
Leave Blank |
B56 = Receiver 2 Phone |
Leave Blank |
|
|
Misc Functions |
|
Program these sections by adding 1 2 3 4 together for sum |
1st section
Zone 1 = 1
Zone 2 = 2
Zone 3 = 4
Zone 4 = 8
|
2nd section
Zone 5 = 1
Zone 6 = 2
Not Used = 4
KP Panic = 8
|
Example: add 1 to 8 together to get total entered section
“088 – 089 Chime Time”, to program Zones 1 2 and 4 for
Chime, add 1 + 2 + 8 = D, enter in section 088, blank 089
|
|
B59 = Day Zone |
_ _ (Leave blank) |
B61 = Priority Zone |
F 3 (By default this is F 3, leave alone) |
B62 = Auto-Bypass |
? ? (Leave alone) |
B63 = Selective Bypass |
F F (Allows Bypassing of Zones |
Note: if Smoke Detector on a Zone disable Selective Bypass for that zone |
B64 = Group Bypass |
? ? |
Note: If a zone is enabled as Group Bypass it can be bypassed
by pressing [B] key twice.
|
B65 = 24 hr Protection |
? ? (Normally don’t program) |
Note: If using Hold-Up buttons on a zone enable this option for that zone |
B66 = Auto Reset |
F 3 (By default this is F 3, leave alone) |
B67 = Abort Delay |
_ _ (Leave blank) |
B68 = Alarm Output |
F 3 (Leave Alone) |
B71 = 10ms Loop Response |
? ? (Leave Alone) |
B72 = 50ms Loop Response |
? ? (Leave Alone) |
B57 = Misc Options |
D _ |
Note: This just enables KP Panic on Zone 5 and Cancel Code |
|
|
System Times |
|
B73 = Output 1 Timout |
1 |
(Siren Timout x5 minutes) |
B75 = Line Seizure Time |
2 |
(2 by default, leave alone) |
B76 = Anti-Jam Time |
3 |
(3 by default, leave alone) |
B77 = Redial Delay Time |
4 |
(4 by default, leave alone) |
B78 = Abort Delay |
_ |
(no time, leave alone) |
B79 = Wait for Handshake |
7 |
(7 by default, leave alone) |
B58 = Redial Attempts |
9 _ |
(9 times, leave 2nd blank) |
|