Ademco Vista XT Program

Enter Program 4140 + 8 + 0 + 0 (Display should show 00, also try 4130 and 5130)
or Power down then back up and press * and # within 1 minute
(If exiting programming you can re-enter within 1 minute by pressing * and #)
Move to Location * + Location
View Location # + Location (Display will read off one digit at a time)
Exit Program *98 OR *99 if needing to re-enter programming later by Code + 8 + 00
Report Codes Zones 1 to 8 alarms send 31 to 38, troubles (optional) send 51 to 58
Zones 9 to 17 alarms send 41 to 49, troubles (optional) send 61 to 69
Duress = 26, Police Panic = 29, Medical Panic = 27, Fire Panic = 28
AC Failure = 79, Low Battery = 78, Cancel = D1
Hex Program Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15
Alpha Keypads can only be 5330 or 5337, cannot use 6139 (NOT required for programming)

*00 Installer Code I_4_I_1_I_4_I_0_I (also try 4130 and 5130)
*01 Master Code I_?_I_?_I_?_I_?_I
*02 Zone Types for Zones 1 to 8
I_?_I_?_I Zone 1
I_?_I_?_I Zone 2
I_?_I_?_I Zone 3
I_?_I_?_I Zone 4
I_?_I_?_I Zone 5
I_?_I_?_I Zone 6
I_?_I_?_I Zone 7
I_?_I_?_I Zone 8
*03 Zone Types for Zones 9 to 16
I_?_I_?_I Zone 9
I_?_I_?_I Zone 10
I_?_I_?_I Zone 11
I_?_I_?_I Zone 12
I_?_I_?_I Zone 13
I_?_I_?_I Zone 14
I_?_I_?_I Zone 15
I_?_I_?_I Zone 16
00 = Disabled
01 = Entry/Exit 1
02 = Entry/Exit 2
03 = Instant
04 = Interior
05 = Day Zone
06 = Holdup
07 = Police
08 = Medical
09 = Fire
10 = InteriorDelay
*04 Zone Type for Zone 17
I_?_I_?_I Zone 17
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
*05 Zone Types for Panics
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Polling Loop Short
I_0_I_8_I 1 & * / A Panic Key (Keypad Medical)
I_0_I_9_I 3 & # / C Panic Key (Keypad Fire)
I_0_I_7_I * & # / B Panic Key (Keypad Police)
*06 Designate Right Loop Zns 10 to 16
    (Hardwire Zone Expander)
I_1_I_1_I_1_I_1_I_1_I_1_I 0 = 4208/4192/4275
1 = 4190WH or 4196
*07 Designate Right Loop Zone 17
    (Zone Expander)
I_1_I 0 = 4208/4192/4275
1 = 4190WH or 4196
*08 Not Used
*09 Entry Delay I_0_I_2_I (0 to 15 x15 seconds)
*10 Exit Delay 1 I_0_I_4_I (0 to 15 x15 seconds)
*11 Entry Delay I_0_I_2_I (0 to 15 x15 seconds)
*12 Exit Delay 2 I_0_I_4_I (0 to 15 x15 seconds)
*13 Alarm Sounder Duration I_0_I_4_I (0 to 15 x2 minutes)
*14 Alarm Sounder Type I_0_I (Must be 0)
*15 Keyswitch Enable I_0_I (1=Yes, 0=No)
*16 Arming Ding I_0_I (0 = Disable, 1 = Enable)
*17 AC Loss Keypad Sounding I_1_I (0 = No, 1 = Yes)
*18 Not Used
*19 Control Alarm Sound I_0_I (1 = Disabled, 0 = Enabled)
*20 Not Used
*21 No Fire Timeout I_1_I (1=Yes, 0=No)
*22 Fire Display I_1_I (1=Yes, 0=No)
*23 Multiple Alarms I_1_I (1=Yes, 0=No)
*24 Tamper Zone 10-17 I_0_I (1=Disabled, 0=Enabled)
*25 Duress in In Hi Speed Frmt I_0_I (1=Disabled, 0=Enabled)
*26 Internal Alarm Sound I_0_I (1=Sweeping, 0=Steady)
*27 Test Report Interval I_0_I 0=No Report
(1 = 12, 2 = 24, 3 = 168 Hrs)
*28 Power up in Prev State I_0_I (1=Yes, 0=No)
*29 Quick Arm I_1_I (1=Yes, 0=No)
*30 Touch Tone Dialing I_1_I (1=Yes, 0=No)
*31 PABX Access Code I_ _I_ _I_ _I_ _I (To dial 9 add here)
*32 Primary Account Number I_0_I_?_I_0_I_?_I_0_I_?_I (2 digit entries)
Hex B = 11, C = 12, D = 13, E = 14, F = 15
*33 Primary Phone Number I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I End Phone with *
# + 11 = *, # + 12 = #, # + 13 = 2.5 second pause
*34 Secondary Phone Number I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
*35 Download Phone Number I_1_I_8_I_0_I_0_I_7_I_6_I_2_I_7_I_8_I_3_I_1_I
*36 Download CSID Number I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I
(15’s Default CSID to Factory)
*37 Download Commands I_1_I Dialer Shutdown
I_1_I System Shutdown
I_0_I Not Used
I_1_I Remote Bypass
I_1_I Remote Disarm
I_1_I Remote Arm
I_1_I Upload Program
I_1_I Dwnld Program
(0=Disabled, 1=Enabled)
*38 Priority Zone I_0_I_0_I (All zones bypassable)
*39 O/C Report 9 to 15 I_0_I_0_I_0_I_0_I_0_I_0_I_0_I_0_I (0=No, 1=Yes)
*40 Program Tamper Report I_0_I_0_I (Disabled)
*41 Normally Closed Zones 2-8 I_0_I (0=EOL, 1=NC)
*42 Dial Tone Pause I_0_I (0 = 5, 1 = 11, 2 = 30 sec)
*43 Dial Tone Detection I_0_I (0 = Disable, 1 = Enable)
*44 Ring Detection Count I_1_I_5_I (15 = Answering Machine)
*45 Primary Ack Wait I_0_I (0=30 sec, 1=60 sec)
*46 Primary Format I_0_I 0 = Ademco Lo
1 = Sescoa/Radionics
2 = Ademco High Speed
*47 Secondary Ack Wait I_0_I (0=30 sec, 1=60 sec)
*48 Secondary Format I_1_I 0 = Ademco Lo
1 = Sescoa/Radionics
2 = Ademco High Speed
*49 Checksum Verify I_0_I (0=No, 1=Yes)
*50 Sescoa Radionics Select I_0_I (0 = Radionics, 1 = Sescoa)
*51 Dual Reporting I_0_I (0=No, 1=Yes)
*52 O/C Rep User 1 to 8 I_1_I_0_I_0_I_0_I_0_I_0_I (0=Disabled, 1=Enabled)
(User 1 must be enabled to allow Installer Code entry into programming)
*53 4/2 Zone Format 17 I_1_I 0 = Non Reported Zone
1 = 4/2 Reporting
*54 4/2 Zone Format 9 I_1_I 0 = 3/1 Ademco Hi Speed
1 = 4/2 Reporting
*55 Alarm Report I_0_I (0=Standard, 1=Expanded)
*56 Restore Report I_0_I (0=Standard, 1=Expanded)
*57 Bypass Report I_0_I (0=Standard, 1=Expanded)
*58 Trouble Report I_0_I (0=Standard, 1=Expanded)
*59 Open/Close Report I_0_I (0=Standard, 1=Expanded)
*60 Low Bat, AC Loss I_0_I (0=Standard, 1=Expanded)
****IMPORTANT for the below reporting to send correctly *46 must be 0 and *53 must be 1****
*76 Channel Assigned to Zones 1 to 8
I_0_I_1_I Zone 1
I_0_I_2_I Zone 2
I_0_I_3_I Zone 3
I_0_I_4_I Zone 4
I_0_I_5_I Zone 5
I_0_I_6_I Zone 6
I_0_I_7_I Zone 7
I_0_I_8_I Zone 8
*72 4/2 Expanded Format Zones 1 o 8
I_0_I_3_I Alarm
I_0_I_5_I Trouble (Optional)
I_0_I_0_I Bypass
I_0_I_0_I Alarm Restore
I_0_I_0_I Trouble Restore
I_0_I_0_I Bypass Restore
*72 is 1st digit of Report code, *76 is 2nd digit, Zones 1 to 8 send Alarm 31 to 38, Trouble sends 51 to 58
*77 Channel Assigned to Zones 9 to 16
I_0_I_1_I Zone 9
I_0_I_2_I Zone 10
I_0_I_3_I Zone 11
I_0_I_4_I Zone 12
I_0_I_5_I Zone 13
I_0_I_6_I Zone 14
I_0_I_7_I Zone 15
I_0_I_8_I Zone 16
*73 4/2 Expanded Format Zones 9 to 16
I_0_I_4_I Alarm
I_0_I_6_I Trouble (Optional)
I_0_I_0_I Bypass
I_0_I_0_I Alarm Restore
I_0_I_0_I Trouble Restore
I_0_I_0_I Bypass Restore
*73 is 1st digit of Report code, *77 is 2nd digit, Zones 9 to 16 send Alarm 41 to 48, Trouble sends 61 to 68
*78 Channel Assigned to Zone 17
I_0_I_9_I Zone 17
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
*74 4/2 Expanded Format Zone 17
I_0_I_4_I Alarm
I_0_I_6_I Trouble (Optional)
I_0_I_0_I Bypass
I_0_I_0_I Alarm Restore
I_0_I_0_I Trouble Restore
I_0_I_0_I Bypass Restore
*74 is 1st digit of Report code, *78 is 2nd digit, Zone 17 sends Alarm 49, Trouble sends 69
*79 Channel Assigned to Panics
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_0_I Not Used
I_0_I_6_I Duress
I_0_I_0_I Polling Loop Short
I_0_I_7_I 1 & * (Medical Panic)
I_0_I_8_I 3 & # (Fire Panic)
I_0_I_9_I * & # (Police Panic)
*75 4/2 Expanded Format Panics
I_0_I_2_I Alarm
I_0_I_0_I Trouble
I_0_I_0_I Bypass
I_0_I_0_I Alarm Restore
I_0_I_0_I Trouble Restore
I_0_I_0_I Bypass Restore
*75 is 1st digit of Report code, *79 is 2nd digit
Duress sends 26, Medical sends 27, Fire sends 28, Police sends 29
*80 – 4 + 2 Expanded Format Non-Alarm Codes *81 – 4 + 2 Expanded Format Non-Alarm Codes
1st Digit
I_0_I_0_I
I_0_I_0_I
I_0_I_7_I
I_0_I_0_I
I_0_I_0_I
2nd Digit
I_0_I_0_I Close Report
I_0_I_0_I Open Report
I_0_I_8_I Low Battery Report (78)
I_0_I_0_I Low Batt Rstr Report
I_0_I_0_I Test Report
1st Digit
I_0_I_0_I
I_0_I_7_I
I_0_I_0_I
I_0_I_0_I
I_1_I_3_I
2nd Digit
I_0_I_0_I Power-Up
I_0_I_9_I AC Loss (79)
I_0_I_0_I AC Restore
I_0_I_0_I Not Used
I_0_I_1_I Cancel (D1)
*82 Swinger Shutdown I_0_I_3_I (00 to 15 Alarms)
*83 Test Report Start I_0_I_0_I (01-31 hrs, 00=Instant)
*84 Kissoff Wait I_0_I (1=Watts Line, 0=No Watts)
*85 DO NOT PROGRAM
*86 Zone Expander Type I_0_I (1=No 4206, 0=Other RPM’s)
*87 Entry Warning I_0_I (1=Continous, 0=No Delay)
*88 Burg Alarm Comm Delay I_0_I (0=No Delay, 1=16 sec)
*89 Alarm Voltage Out Triggers I_0_I 0=No Alarm Trig, Zone Exp
1=Alarm Trig, No Zone Exp
*93 5137 LCD Keypad Programming (See Page 74 of 5130XT Installer Manual for details)
*97 Default Panel (No Value needed, keypad will beep and default panel)