Ademco Vista 100 Program
Enter Program |
5140 + 8 + 0 + 0 + 0 (Display should show 00) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * and #) |
Exit Program | 1. *98 OR 2. *99 if needing to re-enter programming later by Code + 8 + 00 |
Move to Location | * + Location |
View Location | # + Location (Display will read off one digit at a time) |
|
||||||
|
||||||
|
||||||
*00 Installer Code | I_5_I_1_I_4_I_0_I | |||||
*08 Temporal Siren Pulse | I_0_I |
0 = No 1 = Yes |
||||
*09 Entry Delay | I_0_I_2_I | 00 to 15 x15 seconds (Partition-Specific) | ||||
*10 Exit Delay 1 | I_0_I_3_I | 00 to 15 x15 seconds (Partition-Specific) | ||||
*11 Entry Delay 2 | I_0_I_6_I | 00 to 15 x15 seconds (Partition-Specific) | ||||
*12 Exit Delay 2 | I_0_I_8_I | 00 to 15 x15 seconds (Partition-Specific) | ||||
*13 Bell 1 Timeout | I_0_I_4_I | 00 to 15 x2 minutes (Partition-Specific) | ||||
*15 Keyswitch Assignment | I_0_I |
0 = Keyswitch Disabled 1 = Partition 1 to 8 = Partition 8 9 = Silence Bell if Fire Present |
||||
*16 Bell 1 Arming Ding | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
*17 AC Loss Keypad Sounding | I_1_I |
0 = No 1 = Yes |
||||
*19 AC Randomize | I_2_I |
0 = No 1 = Randomize 10 – 40 minutes 2 = Randomize 6 – 12 Hours |
||||
*20 VIP Module Phone Code | I_0_I_0_I I_1_I_1_I |
1st Digit = 01 to 09 2nd Digit = 11 for * 12 for # |
||||
*22 Keypad Panic Enable | I_1_I I_1_I I_1_I |
0 = Disabled (Partition-Specific) 1st Digit = Zone 995 1 = Enabled 2nd Digit = Zone 996 3rd Digit = Zone 999 |
||||
*23 Multiple Alarms | I_1_I |
0 = No (Partition-Specific) 1 = Yes |
||||
*24 Ignore Exp Zone Tamper | I_0_I |
0 = Enable Tamper for RF & RPM 1 = Ignore Zone Tampers |
||||
*25 LRR Burg Trigr ZType 8 | I_0_I |
0 = No 1 = Yes |
||||
*26 Intelligent Test Reporting | I_0_I |
0 = No 1 = No Report if other Reports Sent |
||||
*27 Test Report Interval | I_0_I_2_I_4_I |
000 = Disabled 001 to 999 Hours |
||||
*28 Power up in Prev State | I_1_I |
0 = No 1 = Yes |
||||
*29 Quick Arm | I_1_I |
0 = No (Partition-Specific) 1 = Yes |
||||
*30 Main Dialer Tone Dialing | I_1_I |
0 = No 1 = Yes |
||||
*31 PABX Access Code | I_ _I_ _I I_ _I_ _I I_ _I_ _I I_ _I_ _I | |||||
*32 Primary Account Number |
I_0_I_?_I I_0_I_?_I I_0_I_?_I I_0_I_?_I (2 digit entries) (Partition-Specific) Hex B = 11, C = 12, D = 13, E = 14, F = 15 |
|||||
*33 Primary Phone Number |
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I End Phone with * # + 11 = *, # + 12 = #, # + 13 = 2.5 second pause |
|||||
*34 Secondary Phone Number | I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I | |||||
*35 Download Phone Number | I_1_I_8_I_0_I_0_I_7_I_6_I_2_I_7_I_8_I_3_I_1_I_ _I_ _I_ _I_ _I | |||||
*36 CSID Number |
I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I (15’s Default CSID to Factory) |
|||||
*37 Download Cmnds Enable |
I_1_I Dialer Shutdown I_1_I System Shutdown I_0_I Not Used I_1_I Remote Bypass I_1_I Remote Disarm I_1_I Remote Arm I_1_I Upload Prgrmming I_1_I Dwnld Prgrmming |
0 = No 1 = Yes |
||||
*38 Prevent Zone Bypass | I_0_I_0_I_0_I |
000 = All zones bypassable (Partition-Specific) 001 to 087 = Zone 01 to 32 |
||||
*39 O/C Report for Installer | I_0_I |
0 = No (Partition-Specific) 1 = Yes |
||||
*40 O/C Report for Keyswitch | I_0_I |
0 = No 1 = Yes |
||||
*41 Nrmlly Clsd Zones 3 to 8 | I_0_I |
0 = EOL Resistors 1 = Normally Closed |
||||
*42 Dial Tone Pause | I_0_I |
0 = 5 seconds 1 = 11 seconds 2 = 30 seconds |
||||
*43 Dial Tone Detection | I_0_I |
0 = Pause then Dial 1 = Wait for True Dial Tone |
||||
*44 Ring Detection Count | I_1_I_5_I | 15 = Answering Machine | ||||
*45 Primary Format | I_1_I |
0 = Ademco Lo 1 = Contact ID 2 = Ademco High Speed 3 = Ademco Express |
||||
*46 Low Speed Frmt (Prime) | I_0_I |
0 = Ademco Low Speed 1 = Sescoa/Radionics |
||||
*47 Secondary Format | I_1_I |
0 = Ademco Lo 1 = Contact ID 2 = Ademco High Speed 3 = Ademco Express |
||||
*48 Low Speed Format 2nd | I_0_I |
0 = Ademco Low Speed 1 = Sescoa/Radionics |
||||
*49 Checksum Verify |
|
0 = No 1 = Yes |
||||
*50 Sescoa Radionics Select | I_0_I |
0 = Radionics 1 = Sescoa |
||||
*51 Dual Reporting | I_0_I |
0 = No 1 = Yes |
||||
*52 Stndrd/Expanded Report for Primary |
I_0_I Alarm/Fire Supv I_0_I Restore I_0_I Bypass I_0_I Trouble I_0_I Open/Close I_0_I Low Bat |
0 = Standard 1 = Expanded |
||||
*53 Stndrd/Expanded Report for Secondary |
I_0_I Alarm/Fire Supv I_0_I Restore I_0_I Bypass I_0_I Trouble I_0_I Open/Close I_0_I Low Bat |
0 = Standard 1 = Expanded |
||||
*79 Restore Enable Zone Types 1 to 8 I_0_I Zone Type 1 (Entry/Exit 1) I_0_I Zone Type 2 (Entry Exit 2) I_0_I Zone Type 3 (Perimeter) I_0_I Zone Type 4 (Interior Follower) I_0_I Zone Type 5 (Day/Night) I_0_I Zone Type 6 (24 Hour Silent) I_0_I Zone Type 7 (24 Hour Audible) I_0_I Zone Type 8 (24 Hour Auxiliary) |
0 = No Restoral Report 1 = Restoral Report |
|||||
*80 Restore Enable Zone Types 9 and 10 I_0_I Zone Type 9 (Fire w/o verify) I_0_I Zone Type 10 (Interior w/Delay) |
0 = No Restoral Report 1 = Restoral Report |
|||||
|
||||||
*84 Swinger Shutdown | I_0_I_4_I |
00 = Disabled (Partition-Specific) 01 to 15 = 01 to 15 Alarms |
||||
*85 Enable Dialer Reports |
I_1_I Zone 995 I_1_I Zone 996 I_1_I Zone 999 I_1_I Duress |
0 = Disable (Partition-Specific) 1 = Enable |
||||
*87 Entry Warning | I_1_I |
0 = 3 Beeps (Partition-Specific) 1 = Continuous |
||||
*88 Burg Alarm Comm Delay | I_0_I |
0 = No Delay (Partition-Specific) 1 = 16 seconds |
||||
*89 Restore Report Timing | I_0_I |
0 = Instant 1 = At Bell Timeout 2 = At Disarm |
||||
|
||||||
|
||||||
To access Upper programming press *94, to return to lower programming press *99 the 1 isn’t part of location, to go to a Upper program location press * + 2-digits |
||||||
|
||||||
1*17 Common Lobby Partition | I_0_I |
0 = Disabled 1 = Partition 1 to 8 = Partition 8 |
||||
1*18 Affects Lobby | I_0_I |
0 = Does Not Affect Lobby (Partition-Specific) 1 = Affects Lobby |
||||
1*19 Arms Lobby | I_0_I |
0 = Does Not Arm Lobby (Partition-Specific) 1 = Arms Lobby |
||||
1*20 Exit Error Logic | I_0_I |
0 = No 1 = Bypass E/E & Interior Zones faulted after Exit Delay |
||||
1*21 Exit Delay Reset | I_0_I |
0 = No 1 = Resets Exit Delay to 60 seconds after Zone is Closed |
||||
1*22 Cross-Zoning Pair One | I_ _I_ _I_ _I I_ _I_ _I_ _I | |||||
1*23 Cross-Zoning Pair Two | I_ _I_ _I_ _I I_ _I_ _I_ _I | |||||
1*24 Cross-Zoning Pair Three | I_ _I_ _I_ _I I_ _I_ _I_ _I | |||||
1*25 Cross-Zoning Pair Four | I_ _I_ _I_ _I I_ _I_ _I_ _I | |||||
1*28 RF TX Low Battery Sound | I_0_I |
0 = When Disarmed 1 = Immediate |
||||
1*29 RF TX Low Batt Report | I_0_I |
0 = Disable 1 = Enable |
||||
1*30 RF RCVR Check-In | I_0_I_6_I | 02 to 15 x2 Hours | ||||
1*31 RF xmitter Check-In | I_1_I_2_I | 02 to 15 x2 Hours | ||||
1*32 RF Receiver Type | I_0_I |
0 = Disable 1 = 4281 2 = 5881 |
||||
1*33 Tone w/ Rotory Backup | I_1_I |
0 = Disable 1 = Enable |
||||
1*34 Comm Split Report | I_0_I |
0 = No 1 = Alarms to Primary, others Sec. 2 = O/C/Test Secondary, others Pri. 3 = Fire alarms/troubles Primary, all Sec. |
||||
1*42 Call Waiting Defeat | I_0_I |
0 = No 1 = Yes |
||||
1*43 Perm Keypad Backlight | I_1_I |
0 = No (Partition-Specific) 1 = Yes |
||||
1*44 Wireless Keypad Tamper | I_0_I |
0 = Disable 1 = Lockout RF if tamper detected |
||||
1*45 – Exit Delay Sounder | I_0_I |
1 = Enable (Partition-Specific) 0 = Disable |
||||
1*47 Chime on Bell 1 | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
1*48 Wireless Keypad Part | I_0_I |
0 = Disable 1 = Partition 1 to 8 = Partition 8 |
||||
1*49 Suppress TX Sprv Sound | I_1_I |
0 = Enable 1 = Disable |
||||
1*52 Send Cancel | I_0_I |
0 = No Restriction (Partition-Specific) 1 = Within Bell Timeout |
||||
1*53 Download Callback | I_1_I |
0 = Callback Required 1 = No Callback |
||||
1*57 5800RF Global Arm | I_0_I |
0 = Disable 1 = Enable |
||||
1*58 5800RF Force Arm | I_0_I |
0 = Disable 1 = Enable |
||||
1*60 Zone 5 Audio Alarm | I_0_I |
0 = Disable 1 = Enable |
||||
1*70 Event Log Types |
I_1_I Alarm I_1_I Check I_1_I Bypass I_1_I O/C I_1_I System I_1_I Test Rpt |
0 = Disable Logging 1 = Enable Logging |
||||
1*71 12/24 Hour Time Stamp | I_1_I |
0 = 12 Hour 1 = 24 Hour (Military) |
||||
1*72 Log Printer On-line Mode | I_0_I |
0 = Disable 1 = Enable |
||||
1*73 Printer Baud Rate | I_0_I |
0 = 1200 Baud 1 = 300 Baud |
||||
1*74 Relay Timeout XXX Min. | I_0_I_0_I_0_I |
0 to 127 x2 Minutes Enter relay timeout desired for #80 Menu Mode time-driven event relay command numbers “04/09” and #93 Menu Mode Output Programming output command “56.” |
||||
1*75 Relay Timeout YYY Sec. | I_0_I_0_I_0_I |
0 to 127 Seconds Enter relay timeout desired for #80 Menu Mode time-driven event relay command numbers “05/10” and #93 Menu Mode Output Programming output command “57.” |
||||
1*76 Access Control Relay | I_0_I_0_I |
00 to 16 (Partition-Specific) Relay will be pulsed for 2 seconds whenever code + [0] is pressed. | ||||
|
||||||
To access Upper programming press *94, to return to lower programming press *99 the 2 isn’t part of location, to go to a Upper program location press * + 2-digits |
||||||
|
||||||
2*00 Number of Partitions | I_1_I |
1 = 1 Partition to 8 = 8 Partitions |
||||
2*01 DST Start/End Month | I_0_I_3_I I_1_I_1_I |
00, 00 = Disable DST Start End 01 – 12 = Month |
||||
2*02 DST Start/End Weekend |
|
1 to 7 1 = First 2 = Second 3 = Third 4 = Fourth 5 = Last 6 = Next to Last 7 = Third from Last |
||||
2*05 Auto-Arm Delay | I_1_I_5_I |
00 = Instant (Partition-Specific) 01 to 14 x4 Minutes 15 = No Auto-Arm |
||||
2*06 Auto-Arm Warning Period | I_1_I_5_I |
00 = Instant (Partition-Specific) 01 to 15 Minutes |
||||
2*07 Auto-Disarm Delay | I_1_I_5_I |
00 = Instant (Partition-Specific) 01 to 14 x4 Minutes 15 = No Auto-Disarm |
||||
2*08 Force Arm for Auto-Arm | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*09 O/C Reports by Exception | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*10 Disarming Only During Arming/Disarming Windows |
I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*11 Disarming Outside Window if Alarm Occurs |
I_0_I |
0 = Disable (Only used if 2*10 is a 1) 1 = Enable |
||||
2*18 Enable Go To for Partition | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*19 Use Partition Descriptors | I_0_I |
0 = Disable 1 = Enable |
||||
2*20 Enable J2 Triggers for Part | I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*21 Enable Supervision Pulses For LRR Trigger Outputs |
I_0_I Fire |
0 = Disable I_0_I Burglary 1 = Enable I_0_I Silent panic/Duress |
||||
2*22 Display Fire Alarms of Other Partitions |
I_0_I | 0 = Disable (Partition-Specific) 1 = Enable |
||||
2*23 Display Burg & Panics of Other Partitions |
I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
2*24 Display Troubles of Other Partitions |
I_0_I |
0 = Disable (Partition-Specific) 1 = Enable |
||||
To access Upper programming press *94, to return to lower programming press *99 the 3 isn’t part of location, to go to a Upper program location press * + 2-digits |
||||||
3*00 Check or Trouble Display | I_0_I |
0 = Check Displayed 1 = Trouble Displayed |
||||
3*13 Supv Open & Short | I_0_I |
0 = Supv. on short/trouble on open 1 = Supv. on short or open |
||||
3*14 Waterflow Silence Option | I_0_I |
0 = Silence on Code + 1 1 = Silence on restoral |
||||
3*15 Alarm Bell Sound |
I_0_I Bell 1 I_0_I Bell 2 |
0 = Pulsed 1 = Steady |
||||
3*16 Zone Types 17 & 18 Delay | I_0_I_0_I |
00 to 15 x2 seconds (Waterflow & Fire Supervision) |
||||
3*17 Zone 6 Alt Func (Tamper) | I_0_I_0_I |
0 = Disabled 1 = Enabled |
||||
3*18 ZT 17 & 18 Ext Delay | I_0_I |
0 = Use Delay in 3*16 1 = Multiply 3*16 delay by 4 |
||||
3*19 AUX in Alt Func | I_0_I |
0 = Pins 5 & 9 function per 3*20 1 = Pins 5 & 9 as printer RXD & DTR |
||||
3*20 Trigger Outputs Selection | I_0_I |
0 = Lorra Full Connection 1 = Lorra Limited Connection/Keyswitch 2 = Lorra Fire Connection & 5140LED |
||||
3*21 Max # of Dialer Retries | I_8_I | 1 to 8 attempts | ||||
3*30 Dialer Selection |
I_1_I Main I_1_I Backup |
0 = Disabled 1 = Enabled |
||||
3*31 Backup Dialer Tone/Rotary | I_0_I |
0 = Rotary 1 = Touch Tone |
||||
3*50 Zone Type Restore Enable For Zone Types 16 to 18 16 = Fire w/Verification 17 = Fire Water Flow 18 = Fire Supervisory |
I_1_I Zone Type 16 I_1_I Zone Type 17 I_1_I Zone Type 18 |
0 = Disabled 1 = Enabled |
||||
3*57 Bell 2/Aux Relay Arm Ding |
I_0_I Bell 2 I_0_I Aux |
0 = Disabled (Partition-Specific) 1 = Enabled |
||||
3*58 Bell 2/Aux Relay AC Loss |
I_0_I Bell 2 I_0_I Aux |
0 = Disabled (Partition-Specific) 1 = Enabled |
||||
3*59 Bell 2/Aux Relay Chime Annunciation (Partition-Specific) | ||||||
I_0_I Bell 2 I_0_I Aux |
0 = Disabled 1 = Enabled |
|||||
3*60 Bell 2/Aux Relay Timeout |
I_0_I_0_I Bell 2 I_0_I_0_I Aux |
0 = Disabled (Partition-Specific) 1 = Enabled |
||||
3*61 Aux Relay Function | I_0_I |
0 = Trouble/Supervisory 1 = Alarm/Silenced by Code + OFF 2 = Smoke Detector Reset 3 = Battery Save 4 = Alarm, Silenced by Code + # + 67 |
||||
3*82 Enable Features on P1 | I_1_I | 0 = Disable 1 = Enable |
||||
(Away, Stay, Max, Test, Instant, Chime Functions) | ||||||
3*85 Enable Fire & System Zone Bypass | ||||||
I_1_I |
0 = Not Enabled 1 = Only Installer can Bypass 2 = Only Installer & Master can Bypass |