Ademco 4120OEC Program
Enter Program |
4120 + 8 + 0 + 0 (Display should show 00) or Power down then back up and press * and # within 1 minute (If exiting programming you can re-enter within 1 minute by pressing * & #) |
|
Exit Program | *99 | |
Move to Location | * + Location | |
View Location | # + Location (Display will read off one digit at a time) | |
Hex Program | 10 = A 11 = B 12 = C 13 = D 14 = 14 15 = F | |
Use Caution, this panel allows you into locations that are not on the program sheet! | ||
|
||
*00 Installer Code | I_4_I_1_I_2_I_0_I | |
*01 Master Code | I__I__I__I__I | |
*02 Zones Types 1 to 8 |
I_?_I_?_I Zone 1 Smokes must use Zone 1 (2-wire only) I_?_I_?_I Zone 2 I_?_I_?_I Zone 3 I_?_I_?_I Zone 4 I_?_I_?_I Zone 5 I_?_I_?_I Zone 6 I_?_I_?_I Zone 7 I_?_I_?_I Zone 8 |
00 = Disabled 01 = Entry/Exit 02 = Not Used 03 = Instant 04 = Interior 05 = Day Zone 06 = Holdup 07 = Police 08 = Medical 09 = Fire |
*05 Panic Zone Types |
I_0_I_0_I Not Used I_0_I_8_I 3 & # I_0_I_7_I * & # |
|
*08 NO/NC Sensors |
I_1_I Zone 1 I_1_I Zone 2 I_1_I Zone 3 I_1_I Zone 4 I_1_I Zone 5 I_1_I Zone 6 I_1_I Zone 7 I_1_I Zone 8 |
0 = Normally Closed 1 = Normally Open (Use 0 if Smoke on Zone 1) |
*09 Entry Delay | I_0_I_3_I 00 to 15 x 15 seconds | |
*10 Exit Delay | I_0_I_6_I 00 to 15 x 15 seconds | |
*13 Alarm Sounder Timeout | I_0_I_4_I 00 to 15 x 2 minutes | |
*14 Zone 8 Response Time | I_0_I |
0 = 350ms 1 = 10ms |
*21 No Fire Timeout | I_0_I |
0 = No 1 = Yes |
*25 Disable Duress Express Fmt | I_0_I |
0 = No 1 = Yes |
*27 Test Report Interval | I_0_I |
0 = Disabled 1 = 12 Hours 2 = 24 Hours 3 = 168 Hours (Week) |
*29 Quick Arm | I_1_I |
0 = No 1 = Yes |
*30 Touch Tone Dialing | I_1_I |
0 = Pulse Dial 1 = Touch Tone Dial |
*31 PABX Code | I__I__I__I__I | |
*32 Account Number | I_0_I_?_I_0_I_?_I_0_I_?_I_0_I_?_I | |
(Account 1234 = 01 02 03 04) 10 = A, 11 = B, 12 = C, 13 = D, 14 = E, 15 = F | ||
*33 Primary Phone (12 digits) | I__I__I__I__I__I__I__I__I__I__I__I__I | |
End Phone with * # + 11 = * # + 12 = # # + 13 = 2.5 second pause) | ||
*34 Secondary Phone (12 digits) | I_N_I_O_I_T_I__I_U_I_S_I_E_I_D_I__I__I__I__I | |
*35 Callback (12 digits) | I_1_I_8_I_0_I_0_I_7_I_6_I_2_I_7_I_8_I_3_I_1_I__I | |
*36 CSID Download ID | I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I_1_I_5_I | |
(This resets CSID to default of FFFFFFFF) | ||
*40 Program Tamper Report | I_0_I_0_I 00 to 15 | |
*41 EOL Resistor on Zone 1 | I_0_I |
0 = EOL Supervision 1 = No EOL |
*44 Ring Detect | I_1_I_5_I 01 to 15 | 15 = Answer Machine Over-Ride |
*46 Primary Format | I_0_I |
0 = Ademco Lo Speed 1 = Radionics 2 = 4/2 Ademco Express |
*48 Secondary Format | I_0_I |
0 = Ademco Lo Speed 1 = Radionics 2 = 4/2 Ademco Express |
*49 Checksum Verify | I_0_I |
0 = No 1 = Yes |
*54 4-2 Format | I_1_I |
0 = No 1 = Yes |
*55 Alarm Report | I_1_I |
0 = Standard 1 = Extended |
*56 Restore Report | I_1_I |
0 = Standard 1 = Extended |
*57 Bypass Report | I_1_I |
0 = Standard 1 = Extended |
*58 Trouble Report | I_1_I |
0 = Standard 1 = Extended |
*59 Open/Close Report | I_1_I |
0 = Standard 1 = Extended) |
*60 Low Bat/AC Loss/Test | I_1_I |
0 = Standard 1 = Extended |
*65 Zone Report Codes |
I_0_I_3_I Zone 1 (If Smoke use 01) (Sends 31, Smoke sends 11) I_0_I_3_I Zone 2 (Sends 32) I_0_I_3_I Zone 3 (Sends 33) I_0_I_3_I Zone 4 (Sends 34) I_0_I_3_I Zone 5 (Sends 35) I_0_I_3_I Zone 6 (Sends 36) I_0_I_3_I Zone 7 (Sends 37) I_0_I_3_I Zone 8 (Sends 38) |
|
*66 Panic Report Codes |
I_0_I_2_I Duress (Zone 9) (Sends 29) I_0_I_4_I 3 & # (Zone A/Medical or Fire)(Sends 40) I_0_I_2_I * & # (Zone B/Police) (Sends 2B) |
|
*67 Non Alarm Report Codes |
I_0_I_7_I AC Loss 1st Digit I_0_I_9_I AC Loss 2nd Digit (Sends 79) I_0_I_7_I Trouble (Fire) (Sends 71) I_0_I_9_I Trouble Restore (Fire) (Sends 9 followed by zone number) I_0_I_0_I Bypass I_0_I_0_I Bypass Restore I_0_I_9_I Alarm/AC/Low Bat Restore (Sends 9 followed by zone number) |
|
*68 Misc Report Codes |
I_0_I_0_I Openings (05 If needed) I_0_I_0_I Closings (06 If needed) I_0_I_7_I Low Battery I_0_I_8_I Low Battery 2nd Digit (Sends 78) I_1_I_4_I Test (Sends E0) I_1_I_3_I Cancel (Sends D0) |
|
![]() |