Ademco 4110XMP Program

Enter Program 1. Master Code + 8 + 0 + 0 (Display should show 20)
or Power down then back up and press * and # within 1 minute
(If exiting programming you can re-enter within 1 minute by pressing * and #)
Move to Location * + Location
View Location # + Location (Display will read off one digit at a time)
Exit Program 1. *98 OR 2. *99 if needing to re-enter programming later by Code + 8 + 00

*20 Master Code I_4_I_1_I_1_I_0_I (Default is 4110)
*21 Quick Arm Enable I_1_I 0 = No
1 = Yes
*22 Keyswitch Enable I_0_I 0 = No
1 = Yes
*23 Force Bypass Enable I_0_I 0 = No
1 = Yes
*24 RF House Code I_0_I_0_I 00 = Disabled
01 to 31 if using 5700 Wireless sensors
90 If using 4219 Hardwire Zone Expander
*27 Audible Exit Warning I_1_I 0 = No
1 = Yes
*28 Confirmation of Arming Ding I_0_I 0 = No
1 = Yes
*29 Fire Sounder No Timeout I_1_I 0 = No
1 = Yes
*30 Alarm Bell Timeout I_2_I 1 = 4 minutes
2 = 8 minutes
3 = 12 minutes
4 = 16 minutes
*31 Zone 1 Definition I_?_I (Smoke Detectors must use Zone 5)
0 = Zone Disabled
1 = Entry/Exit
2 = Not Used
3 = Instant/Perimeter
4 = Interior/PIR
5 = Trouble by Day
6 = 24 hr Silent (Holdup)
7 = 24 hr Audible (Police Panic)
8 = 24 hr Auxiliary (Medical)
9 = Fire without timeout (Smokes)
10 = Interior with Delay
*32 Zone 2 Definition I_?_I
*33 Zone 3 Definition I_?_I
*34 Zone 4 Definition I_?_I
*35 Zone 5 Definition I_?_I
*36 Zone 6 Definition I_?_I
*37 Zone 7 Definition (Panic * & #) I_7_I
*38 Entry Delay
Exit Delay = Entry + 15 seconds
I_2_I 1 = 20 seconds
2 = 30 seconds
3 = 45 seconds
4 = 60 seconds
5 = 90 seconds
*39 Zone 3 Response to open I_0_I 0 = 400ms
1 = 10ms
*40 PABX Access Code I_ _I_ _I_ _I_ _I (If 9 is needed to dial add here)
*41 Primary Phone (12 digits)
End Phone with *
I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
# + 11 = * # + 12 = # # + 13 = 2.5 second pause
*42 Secondary Phone I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
Note: Pager only available on VERY new 4110XMP’s,
pager will not work if Account starts with 0
*43 Subscriber Account I_ _I_ _I_ _I_ _I
Note: Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15
*44 Report Format I_7_I 0 = 3/1, 4/1 Ademco L/S Standard
1 = 3/1, 4/1 Radionics Standard
2 = 4/2 Ademco L/S Standard
3 = 4/2 Radionics Standard
6 = 4/2 Ademco Express
7 = Contact ID
8 = 3/1, 4/1 Ademco L/S Expanded
9 = 3/1, 4/1 Radionics Expanded
*45 Phone Sys Select I_1_I 0 = Pulse Dialing
1 = DTMF Dialing
2 = Pulse Dialing, CS on Watts Line
3 = DTMF Dialing, CS on Watts Line
*46 Sescoa/Radionics Select I_0_I 0 = Radionics
1 = Sescoa
*47 15 Sec Burg Dial Delay I_0_I 0 = No
1 = Yes
*48 Periodic Test Message I_0_I 0 = None
1 = 24 Hours
2 = Weekly
*49 Split/Dual Reporting I_0_I
To Primary Phone
0 = All Reports
1 = Alarms, Restore, Cancel
2 = All Reports except Open/Close, Test
3 = Alarms, Restore, Cancel
4 = All Reports except Open/Close, Test
5 = All Reports (Dual Reporting)
The following is only available with very new
6 = All reports except Open/Close
7 = All reports
8 = All reports
9 = All reports except Open/Close
To Secondary Phone
Backup Only
All Other Reports
Open/Close, Test
All Reports
All Reports
All Reports
4110XMP’s, use 6 if programming Pagers
Alarms, Open/Close, Troubles
Alarms, Troubles
Alarms, Open/Close, Troubles
Alarms, Open/Close for Users 5-25, Troubles
*50 Keypad Medical/Fire 1 & * I_1_I
3 & # I_1_I
(Silent, sends 95)
(Audible, sends 96)
(This section may not be available on older models,
display will show EE)
*51 Zone 1 Report Code I_1_I_0_I
*52 Zone 2 Report Code I_1_I_0_I
*53 Zone 3 Report Code I_1_I_0_I
*54 Zone 4 Report Code I_1_I_0_I
*55 Zone 5 Report Code I_1_I_0_I
*56 Zone 6 Report Code I_1_I_0_I
*57 Zone 7 Police Panic Report Code I_1_I_0_I
*58 Zone 8 Duress Report Code I_1_I_0_I
*59 Zone 9 Receiver Fail Report Code I_0_I_0_I
*60 Trouble Report Code I_1_I_0_I
*61 Bypass Report Code I_1_I_0_I
*62 AC Loss Report Code I_1_I_0_I
*63 Low Bat Report Code I_1_I_0_I
*64 Test Report Code I_0_I_0_I
*65 Open Report Code I_0_I
*66 Close Report Code I_0_I
*67 RF Xmtr Low Bat I_0_I_0_I
*68 Cancel Report Code I_1_I_0_I
*69 Group Restores Trouble/Bypass I_0_I
*70 Alarm Restore Code I_0_I
*71 Trouble Restore Code I_0_I_0_I
*72 Bypass Restore Code I_0_I_0_I
*73 AC Restore Code I_0_I_0_I
*74 Low Bat Rest Code I_0_I_0_I
*75 RF Low Bat Restore Code I_0_I_0_I

*76 to *79 available if 4281L (Low) Receiver
*76 to *83 available if 4281M (Medium) or 4281H (High) Receiver or 4219 Hardwire Zone Expander
*76 to *92 available if 4281H (High) Receivers

*76 1st Wireless Zone Definition I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
Zone defines type of sensor Zone 10 to 13 = Delay zone
Zone 14 to 29 = Instant/Burg
Zone 30 to 43 = Interior/PIR
Zone 44 to 45 = Interior w/Delay
Zone 46 to 47 = Instant/Burg
Zone 48 to 55 = Fire/Smoke Detector
Zone 56 to 61 = Day Zone
Zone 62 = 24 hr Audible
Zone 63 = Programmed in *92
*77 2nd Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*78 3rd Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*79 4th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*80 5th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*81 6th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*82 7th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*83 8th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*84 9th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*85 10th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*86 11th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*87 12th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*88 13th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*89 14th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*90 15th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*91 16th Wireless Zone I_?_I_?_I
I_1_I_0_I
Zone Number
Report Code
*92 Zone Response of Zone 63 I_0_I 0, 6, 7, 8, 9 only
*93 Reports Per Armed Period I_0_I 0 = 10 Reports
1 = Unlimited
*94 Download Phone Number I_1_I_8_I_0_I_0_I_7_I_6_I_2_I_7_I_8_I_3_I_1_I_ _I
*95 Ring Count I_# 15_I 0 to #15 #15 = Answer Machine
*96 Reinitialize Download (No Value needed, keypad will just beep and reset CSID and account to all F’s)
*97 Default Panel (No Value needed, keypad will beep and default panel)
*98 Exits Program Mode (Will not allow re-entry with Installer Code + 8 + 0 + 0)
*99 Exits Program Mode (Will allow re-entry with Code + 8 + 0 + 0)