Ademco 4110DL Program

Enter Program 1. Master Code + 8 + 0 (Display should show 20)
or
2. Power down then back up and press * and # within 1 minute
Move to Location * + Location
View Location # + Location (Display will read off one digit at a time)
Exit Program 1. *98 OR 2. *99 if needing to re-enter programming later by Code + 8 + 00
Hex Program Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15

*20 Master Code I_4_I_1_I_1_I_0_I (Default is 4110)
*21 Quick Arm Enable I_1_I 0 = No
1 = Yes
*22 Keyswitch Enable I_0_I 0 = No
1 = Yes
*23 Force Bypass Enable I_0_I 0 = No
1 = Yes
*27 Audible Exit Warning I_?_I 0 = No
1 = Yes
*28 Confirmation of Arming Ding I_0_I 0 = No
1 = Yes
*29 Fire Sounder No Timeout I_1_I 0 = No
1 = Yes
*30 Alarm Bell Timeout I_2_I 1 = 4 minutes
2 = 8 minutes
3 = 12 minutes
4 = 16 minutes
*31 Zone 1 Definition I_?_I Smokes Must be on Zone 5
0 = Zone Disabled
1 = Entry/Exit
3 = Instant/Perimeter
4 = Interior/PIR
5 = Trouble by Day
6 = 24 hr Silent (Holdup)
7 = 24 hr Audible (Police Panic)
8 = 24 hr Auxiliary (Medical)
9 = Fire
#10 = Interior w/Delay (new 4110DL’s only)
*32 Zone 2 Definition I_?_I
*33 Zone 3 Definition I_?_I
*34 Zone 4 Definition I_?_I
*35 Zone 5 Definition I_?_I
*36 Zone 6 Definition I_?_I
*37 Zone 7 Definition
(Panic * & #)
I_7_I 7 = Audible Panic
6 = Silent Panic
*38 Entry Delay Exit
Delay = Entry + 15 seconds
I_2_I 1 = 20 seconds
2 = 30 seconds
3 = 45 seconds
4 = 60 seconds
5 = 90 seconds
*39 Zone 3 Response to Open I_0_I 0 = 400ms
1 = 10ms
*40 PABX Access Code I_ _I_ _I_ _I_ _I (If 9 is needed to dial add here)
*41 Primary Phone (12 digits) I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
End Phone Number with * # + 11 = * # + 12 = # # + 13 = 2.5 second pause
*42 Secondary Phone (12 digits) I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I_ _I
(Pager only available on VERY new 4110-DL’s,
pager will not work if Account starts with 0)
*43 Subscriber Account I_ _I_ _I_ _I_ _I (Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15)
*44 Report Format I_7_I 0 = 3/1, 4/1 Ademco L/S Standard
1 = 3/1, 4/1 Radionics Standard
2 = 4/2 Ademco L/S Standard
3 = 4/2 Radionics Standard
6 = 4/2 Ademco Express
7 = Contact ID
8 = 3/1, 4/1 Ademco L/S Expanded
9 = 3/1, 4/1 Radionics Expanded
*45 Phone Sys Select I_1_I 0 = Pulse Dial
1 = DTMF Dial
2 = Pulse Dial, CS on Watts Line
3 = DTMF Dial, CS on Watts Line
*46 Sescoa/Radionics Select I_0_I 0 = Radionics
1 = Sescoa
*47 15 Sec Burg Dial Delay I_0_I 0 = No
1 = Yes
*48 Periodic Test Message I_0_I 0 = None
1 = 24 Hours
2 = Weekly
*49 Split/Dual Reporting I_0_I
To Primary Phone To Secondary Phone
0 = All Reports Backup only
1 = Alarms, Restore, Cancel All Other Reports
2 = All Reports except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All Reports
4 = All Reports except Open/Close, Test All Reports
5 = All Reports (Dual Reporting) All Reports
The following values are only available with very new 4110DL’s, use 6 if programming Pagers
6 = All reports except Open/Close Alarms, Open/Close, Troubles
7 = All reports Alarms, Troubles
8 = All reports Alarms, Open/Close, Troubles
9 = All reports except Open/Close Alarms, Open/Close for Users 5-25, Troubles
*50 Keypad Medical/Fire I_1_I
I_1_I
1 & * (Silent, sends 95, use as Medical Panic)
3 & # (Audible, sends 96, use as Fire Panic)
(*50 may not be available on older models,
display will show EE when trying to access)
*51 Zone 1 Report Code I_1_I_0_I
*52 Zone 2 Report Code I_1_I_0_I
*53 Zone 3 Report Code I_1_I_0_I
*54 Zone 4 Report Code I_1_I_0_I
*55 Zone 5 Report Code I_1_I_0_I
*56 Zone 6 Report Code I_1_I_0_I
*57 Zone 7 Police Panic Report Code I_1_I_0_I
*58 Zone 8 Duress Report Code I_1_I_0_I
*59 Zone 9 Tamper Report Code I_0_I_0_I
*60 Trouble Report Code I_1_I_0_I
*61 Bypass Report Code I_0_I_0_I
*62 AC Loss Report Code I_1_I_0_I
*63 Low Bat Report Code I_1_I_0_I
*64 Test Report Code I_1_I_0_I
*65 Open Report Code I_0_I
*66 Close Report Code I_0_I
*68 Cancel Report Code I_1_I_0_I
*69 Group Restores Trouble/Bypass I_0_I
*70 Alarm Restore Code I_0_I
*71 Trouble Restore Code I_0_I_0_I
*72 Bypass Restore Code I_0_I_0_I
*73 AC Restore Code I_0_I_0_I
*74 Low Bat Rest Code I_0_I_0_I
*93 Reports Per Armed Period I_0_I 0 = 10 Reports
1 = Unlimited
*94 Download Phone Number I_1_I_8_I_0_I_0_I_7_I_6_I_2_I_7_I_8_I_3_I_1_I_ _I
*95 Ring Count I_# 15_I 0 to #15 #15 = Answer Machine Defeat
*96 Reinitialize Download (No Value needed, keypad will beep and reset CSID and account to all F’s)
*97 Default Panel (No Value needed, keypad will beep and panel will default to factory)
*98 Exits Program Mode (Will not allow re-entry with Installer Code + 8 + 0 + 0)
*99 Exits Program Mode (Will allow re-entry with Code + 8 + 0 + 0)